ZYMBO AATT
Ventilarredo Service Manual – English
Pag. 79
Fan speed:
H
M
L
ST
ST+2
Tr(℃)
ST+3
ST+5
2)
After 30 seconds the fan speed is modulated according to the difference between the room
temperature and the set temperature.
3)
In heat mode, the auto fan speed will operate as according to the following diagram:
M
ST
L
ST+2
Fan speed:
Tr(℃)
After 30 seconds the fan speed is modulated according to the difference between room temperature and
set temperature.
In Auto Fan mode speed correspondence are :
Low speed = 1 speed
Med speed = 3 speed
High speed= 6 speed
Note : pay attention logic in Heating mode is changed we have added also High speed when room
Tr≤Ts-5°C
7.9
DRAIN PUMP
Water float is 2 reed sensor ( 2 levels ) :
1)
When low reed contact is close, water pump would run. When low reed contact is open for 5 seconds,
water pump would stop.
2)
When high reed contact is close , it’s mean there is problem in water drainage discharge or pump
don’t work well , for this reason machine stop to work. Command on board will display Alarm Ea,
and wire wall pad will display E10.
3)
When machine stop to work AUX1-AUX2-MTV1-MTV2 are off.
4)
When high reed contact is open, alarm code disappear, unit would work normally.
H
ST -5
Summary of Contents for Ventilarredo RX-200/ECO
Page 3: ...ZYMBO AATT Ventilarredo Service Manual English Pag 3 1 CERTIFICATION 1 1 CE EMC...
Page 4: ...ZYMBO AATT Ventilarredo Service Manual English Pag 4 1 2 CE LVD...
Page 5: ...ZYMBO AATT Ventilarredo Service Manual English Pag 5 1 3 ROHS...
Page 6: ...ZYMBO AATT Ventilarredo Service Manual English Pag 6...
Page 9: ...ZYMBO AATT Ventilarredo Service Manual English Pag 9...
Page 10: ...ZYMBO AATT Ventilarredo Service Manual English Pag 10...
Page 11: ...ZYMBO AATT Ventilarredo Service Manual English Pag 11 3 2 Med exclusive unit explosion view...
Page 12: ...ZYMBO AATT Ventilarredo Service Manual English Pag 12...
Page 13: ...ZYMBO AATT Ventilarredo Service Manual English Pag 13...
Page 14: ...ZYMBO AATT Ventilarredo Service Manual English Pag 14 3 3 Min ECO unit explosion view...
Page 15: ...ZYMBO AATT Ventilarredo Service Manual English Pag 15...
Page 16: ...ZYMBO AATT Ventilarredo Service Manual English Pag 16...
Page 17: ...ZYMBO AATT Ventilarredo Service Manual English Pag 17 3 4 Med ECO unit explosion view...
Page 18: ...ZYMBO AATT Ventilarredo Service Manual English Pag 18...
Page 19: ...ZYMBO AATT Ventilarredo Service Manual English Pag 19...
Page 21: ...ZYMBO AATT Ventilarredo Service Manual English Pag 21...
Page 22: ...ZYMBO AATT Ventilarredo Service Manual English Pag 22...
Page 24: ...ZYMBO AATT Ventilarredo Service Manual English Pag 24...
Page 25: ...ZYMBO AATT Ventilarredo Service Manual English Pag 25...
Page 27: ...ZYMBO AATT Ventilarredo Service Manual English Pag 27...
Page 28: ...ZYMBO AATT Ventilarredo Service Manual English Pag 28...
Page 30: ...ZYMBO AATT Ventilarredo Service Manual English Pag 30...
Page 31: ...ZYMBO AATT Ventilarredo Service Manual English Pag 31...
Page 33: ...ZYMBO AATT Ventilarredo Service Manual English Pag 33...
Page 34: ...ZYMBO AATT Ventilarredo Service Manual English Pag 34...
Page 36: ...ZYMBO AATT Ventilarredo Service Manual English Pag 36...
Page 37: ...ZYMBO AATT Ventilarredo Service Manual English Pag 37...
Page 47: ...ZYMBO AATT Ventilarredo Service Manual English Pag 47 Main PCB wiring connection scheme...