6.

SPECIFICATIONS

规格

Table 1 Solar Mode Specifications

太阳能模式规格

MODEL

型号

3.2KVA

Normal DC voltage

标称直

48vdc

Fault code 22

故障代码

22

If PV input voltage is

higher than

specification, the

output power will be

derated. At this

time, if connected

loads is higher than

derated output

power, it will cause

overload

如果

PV

入电压高于规格,则
输出功率将降低。这
时,如果连接的负载
高于降额的输出功
率,则会导致过载

Reduce the number of

PV modules in series or

the connected load

减少

串联的光伏模块数量或
减少连接的负载

Fault code 02/03

故障代码

02/03

Output abnormal

(Inverter voltage

below than 190Vac

or is higher than

260Vac)

输出异常

(逆变器电压低于

190Vac

或高于

260Vac

1. Reduce the connected

load

减少连接的负载

2. Return to repair center

返回维修中心

Fault code

01/04/06/08

障代码

01/04/06/08

Internal

components failed

内部组件故障

Return to repair center

回维修中心

Fault code

故障代码

23

Over current or

surge

过电流或电涌

Remove abnormal load

or check PV input

消除

异常负载或检查

PV

输入

Fault code

故障代码

01

Bus voltage is too

high

母线电压过高

Restart the unit if the

error happens again

please return to repair

center

如果再次发生错

误,请重新启动设
备,请返回维修中心

Fault code

故障代码

09

Bus voltage is too

low

母线电压过低

Fault code

故障代码

02/03

Output voltage is

unbalanced

输出电压不平衡

Summary of Contents for GENIXGREEN

Page 1: ...3 2KVA INVERTER 5KWH LFP BATTERY ALL IN ONE SOLAR ESS USER MANUAL...

Page 2: ...UNIT 3 4 AC AC INPUT OUTPUT CONNECTION 3 5 PV PV CONNECTION 3 6 FINAL ASSEMBLY 4 OPERATION 4 1 POWER SWITCH 4 2 OPERATION AND DISPLAY PANEL 4 3 LCD LCD DISPLAY ICONS 4 4 LCD LCD SETTING 4 5 PARALLEL F...

Page 3: ...sconnecting all power supply before any maintaining or cleaning please noted that if you only turn off the unit are not safe enough 4 WARNING Only qualified service persons are allowed to operate this...

Page 4: ...r Charger priority via LCD setting LCD AC 5 Smart battery charger design for optimized battery performance 6 Compatible to mains voltage or generator power 7 Overload Over temperature Short circuit pr...

Page 5: ...Figure 1 Hybrid Power System 2 3 Product Overview...

Page 6: ...nstall this inverter at a visible place in order to allow the LCD display to be read at all times LCD 4 For proper air circulation and heat dissipate make sure there is 20 cm distance from the two sid...

Page 7: ...ion to use appropriate cable for PV module connection To reduce risk of injury please use the proper recommended cable size as below Model Gauge Cable mm2 Torque Value 3 2KVA 10AWG 6 1 2 Nm WARNING Be...

Page 8: ...sc 84A SOLAR INPUT Qty of Panels Total input Power Min in serial 6 pcs max in serial 12 pcs 6 12 6 pcs in serial 6 6 pcs 1500W 9 pcs in serial 9 9 pcs 2250W 12 pcs in serial 12 12 pcs 3000W 9 pieces i...

Page 9: ...ay panel shown in below chart is on the front panel of the inverter It includes three indicators four function keys and a LCD display indicating the operating status and input output power information...

Page 10: ...ration information include fault and warning code Input voltage and frequency information Output voltage and frequency information PV voltage and power information Battery voltage and current informat...

Page 11: ...nput output battery AC charging MPPT parallel date and time peak valley and other function settings MPPT This button includes generation and event This button includes LCD inverter MPPT version LCD MP...

Page 12: ...sufficient for load batteries and solar will supply power at the same time When solar energy and batteries are insufficient or solar energy is unavailable AC power supply power to the load Battery Bat...

Page 13: ...efault 42 0Vdc Settings range from 36V or 18V of 24V of 48V to 50V or 25V of 24V of 48V Settings increase or decrease by 0 1V 42 0Vdc 48V 36V 24V 18V 48V 50V 24V 25V 0 1V Equalized charging voltage de...

Page 14: ...local date and time in your country On grid choose Choose the solar mode first then choose grid mode when in grid mode PV will power load first then extra power feed to AC when PV power is not enough...

Page 15: ...5 Fault Reference Code Fault code Fault event 01 Bus voltage is too high 02 Inverter voltage is too high 03 Inverter voltage is too low 04 Bus soft start failure 05 Overload fault 06 Output short circ...

Page 16: ...ocess LCD LED and buzzer will be active then complete off LCD LED The battery voltage is too low 1 Re charge battery 2 Replace battery No response after power on No indication 1 The battery voltage is...

Page 17: ...red LED is on LED warning code 06 06 Fan fault Replace the fan warning code 05 05 Internal temperature of inverter component is over 100 C 100 C Check whether the environment around the equipment wel...

Page 18: ...ted load Fault code 02 03 02 03 Output abnormal Inverter voltage below than 190Vac or is higher than 260Vac 190Vac 260Vac 1 Reduce the connected load 2 Return to repair center Fault code 01 04 06 08 0...

Page 19: ...tor 1 0 Efficiency DC AC DC AC 92 Frequency 50 60HZ Overload protection MPPT will close immediately as long as the input power is greater than the maximum output power MPPT Max input current 19 6A Max...

Page 20: ...aker Max AC charge current 60A Optional 10A to 60A 10A 60A Efficiency Line Mode 95 Rated R load battery full charged R Transfer Time 10ms Communication WIFI Humidity 0 90 RH No condensing Operation te...

Page 21: ...25mA 200uA Table 4 Inverter Mode Specifications Battery system voltage 51 2V Waveform pure Sine wave Output Voltage Regulation 230Vac 5 Output Frequency 50 60Hz 1Hz Peak Efficiency 90 Power factor 1...

Reviews: