background image

Zakład Wytwórczy Aparatów Elektrycznych Sp. z o.o.

14

4.2. Connecting feeding wires and grounding wire.

Before screwing the rails, the terminals (item 3) of the disconnector should be cleaned of any contamination 
by a method that does not damage the silver coatings. It is recommended to use a soft, lint-free cloth for this 
purpose. Next, one should lubricate the contact surfaces of terminals and rails with a thin layer of acid-free 
vaseline or other conductive grease. The screws (item 2) should be tightened carefully with a torque of 62 Nm 
using two wrenches. When tightening the screws, caution must be maintained to not change the settings of 
the disconnector itself. Slight change to the position of the terminal may cause the apparatus to work improp-
erly.

The earthing conductor should be connected by using a screw (item 4) (torque 54 Nm) placed in the earthing 
point located on the shelf of the disconnector's base frame. The earthing point must be previously greased 
with acid-free vaseline.

4

3

2

1

1. 

Rail 

2.

 Terminal’s screw

3.

 Terminal

4. 

Earthing terminal screw

Figure 10 Screwing the rails and earthing 
conductor

Summary of Contents for ONIIIS

Page 1: ...INSTALLATION AND SERVICE MANUAL Zak ad Wytw rczy Aparat w Elektrycznych Sp z o o ONIIIS Outdoor disconnector Manual No DTR 01 03 02 EN...

Page 2: ...ailure to follow the warning instructions can result in serious personal injury or material damage Only suitably qualified personnel can work on or near the device This personnel must know exactly all...

Page 3: ...eration 7 2 3 Ambient conditions during operation 8 2 4 Nameplate 9 3 ACCESSORIES ADDITIONAL EQUIPMENT 10 4 INSTALLATION AND ADJUSTMENT 13 4 1 Preparation of the supporting structure and assembly ot t...

Page 4: ...h the order Disconnectors are delivered on a transport pallet to which they are screwed When transporting the discon nector excessive shocks should be avoided Disconnectors are delivered to the custom...

Page 5: ...s shaft are loosen for de livery time what allows the earthing knives to be closed with closed disconnector s current path After unpacking the disconnector at the recipient the earthing knives item 1...

Page 6: ...onnector The disconnector should be moved using straps as shown in the figure below Disconnectors should be stored indoors in an atmosphere free from aggressive chemical agents 2 DESCRIPTION 2 1 Appli...

Page 7: ...tor s current path consisting of two fixed contacts item 4 bolted to the insulators and movable contact item 5 The movable contacts of the current path are connected to the main shaft by the driving i...

Page 8: ...The ONIIIS disconnectors are adapted for outdoor operation at ambient temperature from 40 to 40 C and relative humidity to 100 Figure 5 Types of terminals of ONIIIS type disconnector Disconnector ONI...

Page 9: ...2 9 6 3 8 4 10 1 1 Manufacturer 2 Year of production 3 Rated current Ir 800 A 4 Rated duration of short circuit tk s 5 Serial number 6 Rated operating voltage Ur kV 7 Surge test voltage Up kV 8 Rated...

Page 10: ...3 ACCESSORIES ADDITIONAL EQUIPMENT 1 ONIIIS disconnector 2 Manual sliding operating mechanism NNP with fix ing 3 Coupling tie rod 4 Supporting bracket Figure 6 ONIIIS type disconnector with NNP opera...

Page 11: ...Elektrycznych Sp z o o 11 1 ONIIIS disconnector 2 NR5S manual operating mechanism with fixing 3 Coupling tie rod 4 Supporting bracket 5 Clamp Figure 7 ONIIIS disconnector with a wall mounted NR 5S ope...

Page 12: ...ycznych Sp z o o 12 1 ONIIIS disconnector 2 NSL 60 motor operating mechanism with fixing 3 Coupling tie rod 4 Supporting bracket 5 Clamp Figure 8 ONIIIS disconnector with NSL 60 operating mechanism mo...

Page 13: ...t stops causing the disconnector to open When closing the course of action is similar except that the lever movement takes place in the opposite direction 4 1 Preparation of the supporting structure a...

Page 14: ...e grease The screws item 2 should be tightened carefully with a torque of 62 Nm using two wrenches When tightening the screws caution must be maintained to not change the settings of the disconnector...

Page 15: ...visable to do visual inspection of disconnector in each case paying at tention to the correct achievement of limit positions by the apparatus as well as the condition of the insulators contamination m...

Page 16: ...acts with acid free vaseline or other conductive grease replacement of contacts in the case when the surfaces of their mutual contact are significantly damaged tightening of loose screw connections if...

Page 17: ...substances In accordance with applicable regulations it is possible to return a worn out complete disconnector to the manufacturer Zak ad Wytw rczy Aparat w Elektrycznych Sp z o o Current path resist...

Reviews: