background image

INST20

18

_Model350_65-250

  Rev. 

11

/18

ZURN.COM.AU

ZURN WILKINS BACKFLOW

Double Check Valve Assembly

INSTALLATION & MAINTENANCE 

MODEL 350 65-250mm

INSTALLATION INSTRUCTIONS

CAUTION:

 Installation of Backflow Preventers must be performed 

by qualified, licensed personnel. The installer should be sure 

the proper device has been selected for the particular installa-

tion. Faulty installation could result in an improperly function-

ing device.

-

ZURN WILKINS Model 350 Double Check Valve assemblies are

for use on potable water lines where a health hazard does

exist in the event of a backflow situation.

-

Damage to the device could result wherever water hammer

and/or water thermal expansion could create excessive line

pressure. Where this could occur, shock arrestors, check valves

and/or pressure relief valves should be installed downstream

of the device.

-

If installation is in a pit or vault, the Backflow Preventer must

never be submerged in water because this could cause a

cross-connection. Make sure that the pit or vault always

remains dry by providing ample drainage.

1.

Before installing a Model 350 Backflow Preventer, flush the

line thoroughly to remove all debris, chips and other foreign

matter. If required, a strainer should be placed upstream of the

Backflow Preventer. 

CAUTION:

 Do not use a strainer in seldom

used emergency waterlines such as fire lines.

2.

Provide adequate space around the installed unit so that the

test cocks will be accessible for testing and servicing.

3.

Install valve at least 300mm above surrounding flood level.

4.

Always consult local codes for installation methods, approvals

and guidance.

5.

Resilient seated shutoff valves are required to be installed on

both the inlet and outlet of the device to make field testing

possible.

WARRANTY:

 

 ZURN WILKINS Valves are guaranteed against defects of material or workmanship when used for the services recommended. Please

refer to the LWG Zurn/ Zurn Wilkins Product Warranty Statement for details.

PERFORMANCE

1

2

00kPa

60

 

Celsius

2400kPa

MODEL 350 FEATURES

 

Max. Working Water Pressure

 

Max. Working Temperature

 

Hydrostatic Test Pressure

End Connections 

Flanged

  WATERMARK

 AS/NZS 2845.1

     LIC. 1379

TYPE TESTED

 AS/NZS 4020

    LIC. 20111

STANDARDS COMPLIANCE

-

Australian Watermark (AS/NZS 2845.1) Approved Lic. 1379

-

Type Tested AS/NZS 4020 Lic. 20111

PLACING THE DEVICE IN SERVICE

1.

Start with both shut-off valves closed. Slowly open the inlet

shut-off valve until the backflow preventer is completely

pressurized.

2.

When the unit has been pressurized, vent any trapped air by

slightly opening each of the four test cocks.

3.

Slowly open the downstream shut-off valve. The Model 350

Double Check Valve assembly is now in service.

4.

After the Model 350 has been properly installed, test the device

(see “TEST PROCEDURES”). If the device fails the test, remove

the first and second check valves and thoroughly flush the

device. Clean rubber and seats of all debris and place unit back

in service.

65, 80 & 150mm

200 & 250mm

OUTDOOR INSTALLATION: 

The Model 350 Backflow Preventer may be installed outdoors only if the device is protected against 

freezing conditions. Exposure to freezing conditions will result in improper function or damage to the device. The installation location 

must be kept above 0°C. All the basic installation instructions apply.

DIRECTlON OF FLOW �

 

WILKINS MODEL 350 

DIRECTlON OF FLOW � 

WILKINS MODEL 350 

Summary of Contents for 350

Page 1: ...llation methods approvals and guidance 5 Resilient seated shutoff valves are required to be installed on both the inlet and outlet of the device to make field testing possible WARRANTY ZURN WILKINS Valves are guaranteed against defects of material or workmanship when used for the services recommended Please refer to the LWG Zurn Zurn Wilkins Product Warranty Statement for details PERFORMANCE 1200kPa...

Page 2: ...es and water stops running out of test cock 3 5 Close all test cocks open shut off valve 1 and remove test equipment TEST NO 2 TIGHTNESS OF 2 CHECK VALVE REQUIREMENT The static pressure drop across check valve 2 shall be at least 1 0 psid If test cock 4 is not at the highest point of the check valve body then a vertical tube must be installed on test cock 4 so that it rises to the top of the check ...

Page 3: ... side of the seal ring is unused it is possible to invert the seal ring This would be considered a temporary solution to fixing a fouled check and should be replaced with a new seal ring as soon as possible 9 Inspect valve cavity and seating areas Remove any debris 10 Reverse the above procedures to reinstall check assemblies Lubricate seat o rings to hold them in place while reinstalling seat Plac...

Page 4: ...S cont d PROBLEM POSSIBLE CAUSES CORRECTIVE ACTION LEAKING CHECK VALVES 1 Debis on seat or seal ring 1 Clean seat area 2 Damaged seat area 2 Replace check assembly 3 Damaged seat o ring 3 Replace seat o ring 4 Damaged bolt o ring s on check retainer 4 Replace o ring s LOW OR NO FLOW 1 Device installed backwards 1 Verify flow direction arrow 2 Gate valves not fully open 2 Turn handles counter clockw...

Page 5: ...RFORMANCE CHARACTERISTICS MODEL 350 65 80 100mm 0 0 35 69 104 12 6 25 2 37 9 50 5 FLOW RATES l s PRESSURE LOSS kPa 65mm 80mm 100mm MODEL 350 150 200mm 0 35 69 104 25 2 50 5 75 7 100 9 126 2 151 4 FLOW RATES l s 150mm 200mm 0 0 35 69 104 63 0 126 0 189 0 252 0 MODEL 350 200 250mm PRESSURE LOSS kpa 200mm 250mm 0 PRESSURE LOSS kPa FLOW RATES l s ...

Reviews: