ZXG10 iBSC Hardware Installation Guide
c.
Bundle the cables with 150 mm- or 300 mm- long cable clips according to the
number of cables and cut the cable clips flush.
d.
Before laying the power cable and the grounding cable, exactly measure the
distance between two ends, reserve an enough length, lest the cable would be
insufficient in practice. During the cabling, if the reserved length is insufficient, a
longer cable should be used instead and re-distributed. Do not make connectors
or weld midway, as shown in
.
Figure 6-1 Cabling of power cables and grounding cables
2.
Specification of Engineering Labels
The flag-type label made by ZTE itself is used as the engineering identification for
power cables. The label at either end shall contain clear direction for both ends. The
label style is shown in
.
Figure 6-2 Power cable labels
It is pasted at the distance of 2 cm from the lug. First paste the label nearly half of a
circle on the cable, and then paste the backs of two halves of the flag-shaped label
together. One such label should be pasted on both ends of a power cable, as shown
in
6-2
SJ-20110531095035-004|2011-10-28 (R2.0)
ZTE Proprietary and Confidential