background image

10

b) Position-limit switches 

Position-limit switches PO, PZ switch off an electric actuator when the output shaft reaches the position for 

which they are set. Signalling-limit switches SO, SZ signalise the position of electric actuator output shaft. 

The  setting  of  position-limit  switches  is  carried  out  by  positioning  the  output  shaft  into  the  position  in 

whichthe set switch should switch off. Then, loosen the micro-switch cam using the releasing screw.

Loosing will be done by turning the releasing screw counter-clockwise. Turn the releasing screw only until 

the cam is released. By further turning of the releasing screw, you would tighten the cam again. Numbers of 
relevant releasing screws are on a holder of position unit 

(Fig. 1)

 and they correspond to markings on a cam shaft. 

When  loosened,  turn  the  cam  in  the  opposite  direction  to  the  motion  of  an  electric  actuator  output  shaft  while 

setting the position “open” or “closed” until the micro-switch switches over. In this position lock the cam by tightening 
the releasing screw 

(clock-wise direction). 

A signalling switch must be set so that it switches over sooner than a relevant position-limit switches or torque-limit 

switches. When  adjusting  position-limit  and  signalling  switches  of  electric  actuators Type  Nos.  52  326  and  52  327, 
ensure that a gear segment of position and signalling unit drive in the extreme position “open” or “closed” doesn’t hit 
the actuator case. A position unit of electric actuator Type No. 52 325 is not equipped with the locking of cams using 
screws 

(Fig. 2).

 The cam’s position on the shaft is ensured only by friction which has to be overcome when adjusting 

the cams. A design Type No. 52 325 has cams locked by friction and central milled nut with contra-nut which must be 
loosened before adjusting and tightened properly again after adjusting.

c) Position transmitter

To adjust the potentiometer it is sufficient to set the actuator output shaft to any of the OPEN or CLOSED end 

positions.  In  this  way,  the  potentiometer  is  automatically  preset. The  automatic  adjustment  of  the  potentiometer  is 
usually provided already when the stop screws or the position-limit switches are adjusted.

Current position transmitter CPT 1Az – setting

Before  starting  setting  the  current  transmitter  it  is  necessary  to  set  the  end-limit  positions 

(torque  or  position 

switches)

 of the actuator and connect them into the tripping circuit of the electric motor. In case of an external source of 

feeding voltage, verification must be carried out that it does not exceed the maximum value 30 V DC 

(limit value when 

CPT 1Az is still not damaged)

. Recommended value is 18 – 28 V DC. 

Positive pole of the source is connected to the positive pole of the transmitter CPT 1Az; a milli-ammeter of precision 

at least 0.5 % connected into the circuit. The current loop must be earthed in one point. The figure does not show  
the earthing that can be made at any point of the circuit. 

1.   Shift the output shaft into the position Closed. During closing, the current signal value should decrease. If it increases 

release the transmitter body and, by turning of about 180°, shift to the descending part of the outputcharacteristics. Set 
4 mA by fine turning. Tighten the shim plates to secure the transmitter against spontaneousturning.

2.   Shift  the  output  shaft  to  the  position  Open  and  set  20  mA  using  a  potentiometer  on  the  transmitter  body.  The 

potentiometer has a range of 12 revolutions and it has no stops so that it cannot be damaged by furtherturning. 

3.   Once again verify the current value in the position Closed. If it has changed too much repeat the points 1. and 2.  

If the required corrections are large this procedure should be repeated several times. After the setting, securethe 
transmitter against turning and drip the screws with varnish. 

4.   Use a voltmeter to check the voltage on the CPT 1Az terminals. In order to keep linearity of the output signal  

the voltage must not drop below 9 V, not even with off-take 20 mA. If this condition is not met it is necessary to increase 
the feeding voltage 

(within the range of recommend values)

 or to decrease total resistance of the current loop R.

CPT 1Az

U

U

R

mA

V

R

red

51

51

52

52

red

white

white

CPT 1Az

Summary of Contents for MODACT MOK 1000

Page 1: ...all and Flap Valves 10 18 MODACT MOK 63 t n 52 325 MOK 125 t n 52 326 MOK 250 t n 52 327 MOK 500 t n 52 328 MOK 1000 t n 52 329 MODACT MOK CONTROL MOK 1000 t n 52 329 MOK 1000 t n 52 329 MODACT MOK CO...

Page 2: ...ZPA Pe ky a s is certified company in accordance with ISO 90001 as amended...

Page 3: ...flammable and non conductive dust provided that this does not adversely influence their function Here it is necessary to strictly observe SN 34 3205 It is recommended to remove dust as soon as its lay...

Page 4: ...n is 1200 cycles per hour Mean value of loading torque with load factor 25 and surrounding temperature 50 C is not higher than 40 of maximum tripping torque Mv The highest mean value of loading torque...

Page 5: ...r supply voltage for electric actuators should be discussed with the manufacturer Protective enclosure Protective enclosure of actuators MODACT MOK IP 67 according to SN EN 60529 Noise Level of acoust...

Page 6: ...itter 1 x 100 Technical parameters Position scanning resistance Turning angle 0 320 Non linearity 1 Transition resistance max 1 4 Permitted voltage 50 V DC Maximum current 100 mA b Type CPT 1Az passiv...

Page 7: ...internal wiring The internal wiring diagrams of the MODACT MOK actuators with terminal designation are shown in this Mounting and operating instructions Each actuator is provided with its internal wir...

Page 8: ...are marked according to SN IEC 417 34 5550 If actuator is not provided with over current protection when purchased such protection must be provided externally 7 TECHNICAL DESCRIPTION The MODACT MOK M...

Page 9: ...side of the actuator along with the external protective terminal When viewing the stop screws the right hand stop screw is designedfor the CLOSED position whereas the left hand stop screw is designed...

Page 10: ...ometer is automatically preset The automatic adjustment of the potentiometer is usually provided already when the stop screws or the position limit switches are adjusted Current position transmitter C...

Page 11: ...on of the current 20 mA was considerable repeat adjustment for 4 mA and 20 mA once again Disconnect the milli ammeter The screw secured by a drop of varnish situated nearer to the centre must not be t...

Page 12: ...mit switches have been adjusted to the specified torque at the factory If they are required to be readjusted to another torque release the corresponding cam by means of the cam releasing screws whose...

Page 13: ...oltage Speed of rotation of the actuator output shaft is given by the actuator type and variant it cannot be influenced by the regulator Connection of actuator with regulator and three phase electric...

Page 14: ...s and connectors J1 signal terminal board J2 power terminal board 1 test input of logic control signal test A OPEN power output Open 2 GND control signal negative pole B CLOSE power output Close 3 IN...

Page 15: ...mit switch means a position switch or moment switch of actuator connected so that it can stop the actuator motion in given direction During the auto calibration the regulator ZP2 measures the reaction...

Page 16: ...e latest value of the parameter in the particular menu is selected another pressing of the push button SW2 will bring you back again to the first value of this parameter In this way you can select val...

Page 17: ...n case of a change in setting the limit switches of the actuator or a change in mechanical properties of the valve e g if the gland is tightened Menu 6 Auto calibration error messages D 3 yellow D 4 r...

Page 18: ...utput shaft rotates in the correct direction For this check depress the lever of the corresponding position limit or torque limit microswitch depending on the control mode while the actuator operates...

Page 19: ...e faulty parts and adjusting the electromagnetic brake of the electric motor using this brake The brake should be readjusted after 0 5 x 105 switching operations the air gap between the armature and t...

Page 20: ...x 230 0 90 45 MOK 63 MOK 125 MOK 250 MOK 500 MOK 1000 52 325 52 326 52 327 52 328 52 329 FCJ2B52D FCT2B54D FT2B52D FCJ2B52D FCJ4C52N FCT4C54N FT4C52NA EAMR56N04A FCJ4C52N FCT4C54N FT4C52NA EAMR56N04A...

Page 21: ...ositioned at a 45 basic basic positioned at a 45 positioned at a 45 basic positioned at a 45 basic positioned at a 45 basic positioned at a 45 basic basic positioned at a 45 positioned at a 45 basic p...

Page 22: ...4 16 16 19 19 0 1 2 3 4 5 6 7 8 9 W 0 1 2 3 4 5 6 7 8 9 W collar exchangeable inserts lever not available exchangeable inserts lever basic basic positioned at a 45 positioned at a 45 basic ppositioned...

Page 23: ...23 Lever adapter with Type No 52325 actuator 386 367 301 P P pohled na z kladn desku M2 1 61 49 26 120 3 x 1 1 5 view of the base plate...

Page 24: ...24 Lever adapter with Type No 52326 actuator 376 418 388 20 140 90 70 3 x 1 4 P P pohled na z kladn desku M2 1 Note Other dimensions are listed in the dimension table view of the base plate...

Page 25: ...347 252 290 200 111 263 73 128 F 10 F 07 MOK 500 250 290 386 398 325 362 250 128 73 F 12 F 10 MOK 1000 250 290 386 398 325 362 250 128 323 73 155 F 12 Note Connecting of actuators with connector on s...

Page 26: ...15 1 11 14 1 16 1 12 16 1 19 1 14 18 1 22 1 16 21 2 23 1 17 22 2 26 1 19 25 2 30 1 22 28 2 33 1 24 32 2 37 1 27 36 2 37 1 27 36 2 44 1 32 42 2 A Square end joint in the basic posistion B Square end j...

Page 27: ...DCPT ZP2 RE Microcomputer position regulator KO Directional relay for the OPEN direction KZ Directional relay for the CLOSE position F Thermal safety F Thermal relay R1 R2 2x resistance protection 10...

Page 28: ...ctuators with a one phase motor with the current transmitter without built in power supply or without transmitter with local control or without local control with the current transmitter with built in...

Page 29: ...er and built in power supply with local control or without local control with the resistance transmitter without local control or with local control P 0872 E P0762V1 P 0834 Control phase Control phase...

Page 30: ...5 1000 electric actuators with a one phase motor with the resistance transmitter and local control or without local control with the resistance transmitter and local control or without local control w...

Page 31: ...th local control or without local control Wiring diagrams of MODACT MOK 125 1000 electric actuators with a one phase motor with the current transmitter without built in power supply or without transmi...

Page 32: ...ocal control or without local control with the current transmitter without built in power supply or without transmitter with local control or without local control Wiring diagrams of MODACT MOK 125 10...

Page 33: ...ol electric actuators with the one phase motor and position regulator P 0785 EZ MOK125 1000 1f motor Z2 N U2 17 5 4 9 7 6 8 13 11 12 10 16 15 14 23 20 18 19 22 21 27 25 26 24 28 R2 R1 C M 1 N L1 PE PO...

Page 34: ...variant bez BMO 80 SA1 M D SA2 OTV ZAV L1 nap jen P0920 EZ N V W RZ RO U2 W2 V2 L2 L3 N PE 11 5 9 A B 10 7 6 B 9 10 11 5 A 3 3 7 6 Finder TEST d c sign l 0 4 20 mA 0 10 V Porucha max 24 V 2 W q 56 34...

Page 35: ...a single point of one of the three circuits while other circuits should not be connected to the earth Analog signals should be transmitted via a screened conductor At the signal source the screening s...

Page 36: ...ing between the control section cover and the power unit box for actuators Type Nos 52 325 Packing 224648301 Packing between the control section cover and the power unit box for actuators Type Nos 52...

Page 37: ...NOTE...

Page 38: ...NOTE...

Page 39: ...turn actuators MODACT MO EEx MOED EEx Explosion proof electric multi turn actuators MODACT MOA Electric multi turn actuators for nuclear power stations application outside containment MODACT MOA OC E...

Page 40: ...tel 420 321 785 141 9 fax 420 321 785 165 420 321 785 167 e mail zpa zpa pecky cz ZPA Pe ky a s t 5 kv tna 166 289 11 PE KY Czech Republic www zpa pecky cz...

Reviews: