12. PANEL SPECIFICATIONS
12.1 ENCLOSURE SPECIFICATIONS
DESCRIPTION VALUE
ENCLOSURE SIZE
355 x 275 x 100 mm
TOP CABLE ENTRIES
12 x 19mm DIA GROMMETED ENTRIES
BOTTOM CABLE ENTRIES
2 x 19mm KNOCKOUT ENTRIES
REAR CABLE ENTRIES
2 SNAP OUTS, 60 x 20mm
12.2 ELECTRICAL SPECIFICATIONS
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
230V AC +/- 10% @ 50/60 Hz
BATTERY VOLTAGE
24V DC (2 X 12V SLA BATTERY)
SYSTEM VOLTAGE
24V DC NOMINAL (18 – 32 V)
SYSTEM VOLTAGE RIPPLE
2V PK-PK MAX
CHARGER SIZE
UP TO 7AH in 24 Hours
ZONE VOLTAGE
21V DC NOMINAL (20 - 22.5V)
SOUNDER ALARM OUTPUTS
4 x 150mA @ 29V DC (Nominal)
AUXILIARY FAULT OUTPUT
Via add on relay PCB
AUXILIARY FIRE OUTPUT
1 x RELAY SELV (1A MAX)
NUMBER OF ZONES
1/2/4/6/8
MAXIMUM ZONE CAPACITY
32 DEVICES PER ZONE
MAXIMUM ZONE RESISTANCE
70 ohms
AUXILIARY SUPPLY
200mA @ 29 V dc (NOMINAL)
SOUNDER ACTIVATION DELAY
0-9 MINUTES -IN 1 MIN INCREMENTS
ZONE END OF LINE DEVICE
100uF CAPACITOR (- STRIPE TO ZONE -VE)
SOUNDER END OF LINE DEVICE
10 K RESISTOR
CHARGER VOLTAGE
28.4V @ 25
o
C (NO BATTERY CONNECTED)
CHARGER SHORT CIRCUIT PROTECTION
Batteries less than 20V
TOTAL CHARGER OUTPUT
1.1 Amp