background image

MDPA2 FCA112515 

 

©2012-2015 ZONEFIRST 

®

  

 

Page 4 

 

 

TROUBLESHOOTING 

The MDPA2/MDP3 is a very simple control to troubleshoot, especially 

with the LED indicators.  The only other device needed is a simple 

Volt/Ohm meter.   Almost all problems can be traced to an external 

component or wiring to/from the MDPA2.  The following procedures 

can help isolate the problem. 

 

 

Zone(s) Not Calling 

Each zone has a LED next to the zone damper plug-in jack, when a 

zone is calling and that call is being recognized by the MDPA2/MDP3 

that zone LED will be illuminated GREEN .  Provided no other zone is 

calling for the opposite mode, check the zone that  is supposed to be 

calling and the zone’s LED.  If it is not on, check for 24VAC across 

the thermostat terminal C and the Y, if a Cool call, W if a Heat Call, or 

G if a Fan call.  If there is no voltage here at the panel, the panel is 

not getting the signal from the thermostat.  The problem is mis-wiring, 

a broken wire or a problem in the thermostat.  To check the zone on 

the panel, place jumper from R to Y, R to W or R to G to see that the 

panel is operating properly.   

 

 

Zone(s) Will Not Shut Off 

If a zone will not stop calling, the Zone LED should still be illuminated 

GREEN.  Depending on the call disconnect the Y, W or G wire from 

the terminal strip.  The zone will drop out.  Check the thermostat 

wiring for a mis-wiring or short that keeps the zone calling.   If the call 

remains and the thermostat is disconnected, replace the panel.   

 

 

Damper Motor Checkout 

To checkout the dampers, the panel has a LED for each zone.  This 

illuminates GREEN when the dampers are to be OPEN, either on a 

call or when all zones are satisfied.  The damper position is confirmed 

by the bi-color LED on the motor.  When the panel zone LED is 

Green, the motor LED must be Green also indicating the damper 

being open.  When the panel LED is not lit the damper  should be 

closed and this is confirmed by the damper LED being Red

.   

 

 

Power LED Not On 

If the Power LED is not Illuminated GREEN and there is 24VAC at the 

transformer terminals, the MDPA  has a built-in thermal  fuse, (light 

brown rectangle component below transformer terminals) that may be 

open.  To check, touch to see if component is hot.  If it is hot, fuse is 

open and must be reset.  This is also indicative of a potential wiring 

short.   

 

Remove all wires  (start with transformer wires)  from the MDPA2 

panel and check fuse (must be cool to the touch) to make sure it is 

not hot.  Place 24VAC wires back to transformer terminals on panel 

and power LED should come back on.  If it does not, replace board.  

If it does light, begin adding the wires from each zone to the panel 

one by one checking the power LED at each point.  If the power LED 

drops again check these wires for a potential short.   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER PHASING 

When using separate transformers to power the MDP3 and MDPA2 

panels it is required that all transformers be in phase with one 

another.  To check the transformer phasing use a voltmeter and 

check for voltage on one leg of the 24V transformer connection on the 

MDP3 panel to the opposite leg of the 24V transformer connection on 

the  MDPA2  panel.  See the diagram below.  The voltmeter should 

read zero (0) Volts.  If the voltmeter reads 24V or 48V, reverse the 

leads of one of the transformer until the voltmeter reads zero (0) volts.  

Reading zero volts proves the transformers are in phase with one 

another.   

 

 

 

 

 

 

           MDPA2 Panel Wiring Diagram 

 

 

 

 

 

  

 

 

20 Bushes Lane 

 Elmwood Park, New Jersey 07407-3204 

USA 

              Telephone 1.877.604.1044      FAX 1.201.794.1359 

www.zonefirst.com 

[email protected] 

 

C

 

24VAC 2

 

24VAC 1

 

C

 

24VAC 

 

24VAC

 

0V

 

AC

 

MDP3

 

MDPA2 

24V 40VA

 

Transformer

 

Voltmeter

 

 

 

24VAC 2

 

24VAC 1

 

 

24VAC 2

 

24VAC 1

 

0V

 

AC

 

 

 

24V 40VA

 

 

Voltmeter

 

Reviews: