background image

4

© Copyright 2013 Zoeller Co. All rights reserved.

INSTALLATION

be moved on the discharge pipe or the rubber stops can be adjusted as 

necessary. Cut extra float rod length below lower float stop to prevent 

debris from interfering with float operation.

 12.  If the old primary pump discharge piping is being replaced with PVC 

piping, duplicate the old pipe dimensions and use the existing drainage 

connection.  If the primary pump and backup pump is a new installation, 

the drainage connection must be determined and the discharge pipes 

fitted accordingly.  Solvent weld the upper portion of the discharge pipe 

into the PVC tee outlet (see figures 1 and 2).  Connect the discharge 

pipe into the drainage connection.  The pipe must be supported from 

above to ensure adequate support for the pump assembly.  Reinstall 

pumps in sump pit with discharge back to its original position.

 13.  Install DC control charger (see figure 3) by using the wall bracket and 

anchors provided.  If more convenient, the control charger may be set 

on a nearby shelf or ledge.  The control charger should be located 3 or 

4 ft. above the sump.  To reduce noise from vibration, it is recommended 

that the charger be anchored with the wall bracket provided.  

 14.  Connect the leads from the control charger to the battery terminals.  

Red pos. (+) lead to positive terminal and black neg. (-) lead to negative 

battery terminal.  Upon proper connection, test alarm will sound.  

Press alarm reset to silence.  This indicates proper charger to battery 

connection. 

 Correct battery hook up is essential for 

operation of the system.  Use wing nuts supplied with battery and eyelet 

connectors on battery wire leads.  The positive terminal is the larger 

stud, 3/8" diameter.  The smaller stud, 5/16" diameter is the negative 

terminal.  Apply grease to the terminals to help prevent corrosion.

 15.  Connect the black lead from the pump to the negative (-) battery 

terminal.  Connect the white or red lead from the pump to the white lead 

from the switch.  This connection is made at the fuse installed on the 

switch wire (see figure 3).  Connect the black lead from the switch to the 

positive (+) battery terminal.

 16.  Connect the blue sensor wire to the sensor connector (figure 3).  
 17.  Close battery box and secure cover.  Carpeted or wood barrier between 

the battery case and the floor is recommended.

 18.  Plug the control power cord into the 115V wall outlet.  The primary sump 

pump and the control box should be on separate circuits.

 19.  Reconnect power to primary sump pump.

  1.  The preferred method of installation for backup pumps is shown in 

figures 1 and 2.  The installation kit includes the necessary fittings and 

one check valve for installing with the backup  pump discharging into the 

primary pump outlet pipe.  An additional check valve is incorporated in the 

discharge of the backup pump.

  2.  Remove all parts from shipping carton and make sure all parts are 

included.  Refer to checklist on page 3.

  3.  Select location for battery and control charger.  Control charger must be 

within 6' of a 115V wall outlet and within 6' of pump and basin.  Connect to 

a separate circuit, different than the primary pump.

  4.  If primary pump is installed, disconnect power.  If the primary pump is 

a column pump with adjustable float, and you are installing per figure 2, 

check the “on” point and adjust to approximately 7 ½" from bottom of pump 

(see figure 2).   Mark the discharge pipe 7" above the “on” point of the 

primary column pump or 7" above the top of the primary submersible pump.

  5.  If  existing  discharge  pipe  is  metal  or  flexible  tubing,  it  will  need  to  be 

replaced with SCH. 40 PVC piping.  Use a male adapter for connecting to 

the primary pump outlet.

  6.  Remove the discharge pipe and cut off at the mark determined in step 4.  

Remove an additional 8" from the bottom portion.

  7.  Screw the discharge pipe into the primary pump outlet.  Tighten with 

strap wrench.

  8.  Assemble discharge fittings per figure 4.  Note:  Pump must be glued into 

tee fitting on a 30° angle to avoid air locking (see figure 4).  Rotate pump 

while gluing until the line on the discharge is facing up.  Use a commercial 

grade of PVC cleaner and solvent cement (not furnished with kit) on the 

socket joints.  

  9.  Install the pump and discharge assembly per figure 1 or 2.
 10.  Assemble the float assembly per figure 5.
 11.  Install the float switch assembly bracket above the outlet tee using the 

clamp provided (see figures 1 and 2).  Make certain the clamp is tight on 

the pipe to avoid slippage.  Use electrical tape below the clamp to help 

prevent the clamp from moving.  Ensure that the “off” level of the float is 1" 

min. above the discharge tee of the DC backup pump (see figures 1 and 

2). Position pumps in the sump and move float up and down, making sure 

of free movement without interference from any obstructions inside the 

sump or lid.  Very shallow sumps may require some adjustment to avoid 

overfilling or backing up of water into the sump inlet.  The float switch can 

INITIAL START-UP AND OPERATION

  1.  Test the installation for leaks by running water into the sump allowing 

for normal operation of the primary pump.

  2.  Check the control charger. The “red” power on light will be lit when the 

unit is plugged into the 115V wall outlet. The “yellow/green” light will 

indicate the condition of the battery.

  3.  Disconnect primary pump before touching any component in the 

sump pit.

  4.  Lift float switch. The DC backup pump will run and the alarm will sound. 

Lower float switch immediately after pump has started running. Pump is 

running dry during initial check out for several seconds. 

 

Continuous dry running may cause overheating and damage the pump 

seals. Upon release of the float switch, the pump will shut off. Press the 

reset button to turn the alarm off.

  5.  Complete the final testing of your installation by disconnecting the power 

to the primary pump and the control charger by removing the plugs from 

the 115V wall outlets. Run water into the sump until the DC backup 

pump is activated by the float switch. Check all connections for leaks.

  6.  Push alarm reset switch when pump is running. This will silence the alarm. 

The pump will continue to run.

  7.  Reconnect the control charger and your primary pump to the AC wall 

outlets. The primary pump should come on and lower the water level in 

the sump back to the normal operating level and shut off. Both primary 

and backup systems are now ready for use.

  8.  The battery charged and charging LED’s will alternate during normal 

charging operation.

Summary of Contents for Basement Sentry Series

Page 1: ...nown to the state of California to cause cancer and birth defects or other reproductive harm 1 Make sure there is a properly grounded 115V receptacle available Do not use primary pump circuit The location must be within 6 of the control box and battery The power supply for your DC control system plugs directly into the 115V outlet Do not use an extension cord 2 Make sure the 115V electrical supply...

Page 2: ...warranty valid only when a complete system is purchased and used as a backup to a primary dewatering system A complete system includes a Model 507 or 510 Basement Sentry and an Aquanot Battery 1 Inspectandtestthesystemforproperoperationsatleastevery3months a Red power on indicator light should be on indicating AC power is on b Unplug primary pump and the control charger from power supply c Fill su...

Page 3: ...A CHECKLIST PERFORMANCE The DC emergency pump system requires a good quality 12 volt battery to obtain maximum pumping time during a power outage A deep cycle 12 volt 105 amp hour marine battery or larger is recommended and will provide approximately 7 hours of continuous pumping time in a sump pump installation with 8 of head pressure In most installations the pump runs intermittently and the bat...

Page 4: ...primary pump 4 If primary pump is installed disconnect power If the primary pump is a column pump with adjustable float and you are installing per figure 2 check the on point and adjust to approximately 7 from bottom of pump see figure 2 Mark the discharge pipe 7 above the on point of the primary column pump or 7 above the top of the primary submersible pump 5 If existing discharge pipe is metal o...

Page 5: ...g NOTE Pump must be mounted on a 30º angle to avoid airlocking OUTLET PUMP PRIMARY 1 MIN IMPORTANT OFF LEVEL OF FLOAT ASSEMBLY MUST BE HIGHER THAN DC BACKUP PUMP VERIFY WEEP HOLE IS PRESENT IN MAIN DISCHARGE LINE SEE PUMP INSTALLATION INSTRUCTIONS BATTERY BOX BATTERY BOX OUTLET PRIMARY PUMP IMPORTANT OFF LEVEL OF FLOAT ASSEMBLY MUST BE HIGHER THAN DC BACKUP PUMP 1 MIN SK2499 SK2500 ...

Page 6: ...USER FIG 5 DC BACK UP PUMP CLAMP FLOAT SWITCH BLACK WITH RED TRACER TO POSITIVE BLACK LEAD TO POSITIVE WHITE LEAD TO DC PUMP BLACK LEAD TO NEGATIVE TO FLOAT RED LEAD 15 AMP FUSE DC CONTROL BOX BLACK LEAD TO NEGATIVE TO FLOAT SWITCH BLUE LEAD SPLICER WHITE OR TOP VIEW IMPORTANT MAKE SURE THIS LINE IS GLUED IN POINTING UP 1 11 6 SUPPLIED BY CUSTOMER DISCHARGE PIPE ...

Page 7: ...ance free AGM battery which can run the pump continuously for over 7 hours These times are based on continuous pumping at 10 of static head Actual times will vary depending on static head volume of water entering the pit and the condition of the battery Follow these recommendations Use a B C I size 27 deep cycle battery 175 minute reserve capacity or larger Do NOT use a maintenance free battery un...

Page 8: ...hat accompany the detector nor do they supersede advice from the CO detector manufacturer If the audible alarm associated with your CO detector is activated we recommend the following actions 1 Take immediate action for personal safety as recommended in the CO detector literature 2 Contact the appropriate agency to determine if the CO is being produced by your furnace water heater or any other dev...

Reviews: