background image

4

© Copyright 2013 Zoeller Co. All rights reserved.

  1.  Test the installation for leaks by running water into the sump allowing for normal 

operation of the primary pump.

  2.  Check DC pump backup control system as follows. Refer to fig. 6.
 

(a)  Continuous “Red” light indicates power supply is “on”.

 

(b)  “Yellow”/“Green” light is the battery indicator light. A continuous yellow glow 

indicates the battery is being charged. This turns to “Green” when battery is 

fully charged. Upon full charge, it is normal for this light to alternate between 

Yellow and Green.

 

(c)  Reset lower toggle and lift float switch. DC - pump will run, “Yellow” pump 

run indicator light will flash and continuous alarm will sound. Release float 

switch immediately after pump has started running. Pump is running dry 

during initial check out for several seconds. 

 Continuous 

dry running may cause overheating and damage to the  pump seals.

 

(d)  Upon release of float switch, pump will shut “off”, alarm will shut “off”, “Yellow” 

pump run indicator light will stay “on”. Turn off the “Yellow” pump light by 

pushing the toggle switch down for less than 3 seconds. The alarm will beep 

twice indicating the system has been reset. The “Yellow” light indicates the 

emergency pump has operated to relieve a flooded  sump and should be 

reset with the toggle switch after the emergency situation has been cleared 

up and water level in the sump has dropped below  the “off” point.

 

(e)  Alarm “on/off” switch is for the convenience of the owner. If the alarm 

becomes an annoyance when the emergency pump is running it can be 

silenced by pushing the toggle switch up. The yellow pump silence indicator 

is a reminder light to indicate the alarm is in the “off” position. The “Yellow” 

pump run indicator light will continue to function and indicate when pump 

is running or has been running.

 

(f)  The control box will activate an alarm signal if the battery is weak.  The 

alarm will sound at a fast rate and will continue until the battery is partially 

initiAL StARtup AnD opeRAtion

  1.  Remove all parts from shipping carton and make sure all parts are included. Refer 

to checklist on page 2.

  2.  Select location for battery and control box. Control box must be within 6' of a 115V 

wall outlet and within 6' of pump and basin.

  3.  If primary pump is installed, disconnect power. If the primary pump is a column 

pump with adjustable float, check the “on” point and adjust to approximately 7½" 

from bottom of pump (see fig. 2). Mark discharge pipe 8-3/8" from the “on” point 

of the primary pump (see Fig. 1 & 2). 

  4.  If existing discharge pipe is metal or flexible tubing, replace with 1½" rigid PVC 

sch. 40 pipe. If replacing a metal pipe with PVC, use a male adapter for connecting 

pipe to primary pump outlet.

  5.  Remove the discharge pipe and cut off at the mark determined in step 3. Remove 

an additional 7-3/16" from the upper portion of the discharge pipe for installing 

the pipe loop for the DC pump. (See Fig. 1 & 2).

  6.  Remove screen from bottom of DC pump by pushing two red lock tabs inward 

and pulling screen free from pump. Bolt the mounting bracket (item 10, fig. 3) to 

the bottom of the pump screen. Use #10-24 screws, washers and nuts provided. 

Make sure the bracket is 90° to the pump discharge. Snap screen and bracket 

onto pump. (See figs. 1 and 2).

  7.  Screw the discharge pipe into the primary pump outlet. Tighten with strap wrench. 

Install the DC pump onto the discharge pipe by using the S.S. worm drive clamp 

provided in the mounting kit (item 10, fig 3). The bottom of the DC pump should 

be located 5-3/8" from the end of the discharge pipe. (See fig. 1 and 2).

  8.  Assemble the pipe loop (items 4 thru 9 as shown in fig. 3). Use a commercial 

grade of PVC cleaner and solvent cement (not furnished with kit) on all the socket 

joints. Tighten all pipe clamps, except lower clamps on rubber couplings, (items 

6C fig. 3), used for connecting the pipe loop to the discharge pipe and pump (see 

figs. 1 and 2).  

  9.  Install the pipe loop assembly, using the rubber couplings and clamps (items 6C 

fig. 3). Tighten all clamps.

 10.  Install the float switch assembly on the lower leg of the discharge outlet tee using 

the clamp provided (see fig. 1 and 2).  Set tether length to 4". Position pumps in 

the sump and move float up and down, making sure of free movement without 

interference from any obstructions inside the sump or lid. Very shallow sumps 

may require some adjustment to avoid overfilling or backing up of water into 

the sump inlet. The float switch can be lowered on the discharge pipe or the 4" 

tether length can be reduced to 3½" min.

  11.  If the old primary pump discharge piping is being replaced with PVC piping, duplicate 

the old pipe dimensions and use the existing drainage connection. If the primary 

pump and backup pump is a new installation the drainage connection must be 

determined and the discharge pipes fitted accordingly. Solvent weld the upper 

portion of the discharge pipe into the PVC tee outlet (see fig. 1 and 2). Connect 

the discharge pipe into the drainage connection. The pipe must be supported from 

above to assure proper alignment of the DC pump loop.

 12.  Install DC control box in suitable location by using the wall bracket and anchors 

provided. (See fig. 5). Place fully charged battery in plastic battery box.

 13.  With the AC power REMOVED, connect the chargers’ positive output lead to 

the positive post of the battery. Connect the chargers’ negative output lead to 

the negative post of the battery. Install the fuse into the yellow “in-line” fuse 

holder. At this point, the chargers’ “correct connection announcement” should 

be observed. The “correct connection announcement” is an audible “beep” 

and several LED flashes. If the “correct connection announcement” does not 

occur, it is possibly due to power fluctuations when the fuse was installed. To 

alleviate this condition, disconnect the fuse for approximately 15 seconds and 

then cAReFuLLy reinstall the fuse into the fuse holder. The “correct connection 

announcement” should be observed.

 14.  Apply grease to battery terminals to help prevent corrosion.
 15.  Close battery box and secure cover. 
 16.  Connect the plugs from the pump and the float switch to the control box terminals. 

Refer to fig. 5 and 6 for location of each terminal plug.

 17.  Plug the control power cord into 115V wall outlet.  The primary sump pump and 

the control box should be on separate circuits.

 18.  Reconnect power to primary sump pump.

inStALLAtion

recharged back to an operating level for the pump. The “Red” signal light 

will blink when the alarm sounds.  The alarm will continue at a fast pulse if 

the battery becomes too weak for normal operating of the pump.  The pump 

will automatically shut off until the battery is recharged. The alarm will sound 

at slower rate as battery becomes recharged to a usable level for pumping. 

The red low-battery light will also pulse at a slower rate.

 

(g)  If an extended power outage occurs a battery may be drained below the 

power level required for operation of the pump.  If more than seven hours of 

continuous run time is required.  Two or more batteries should be connected 

in parallel to extend the run time hours.

 

(h)  After power is restored your “Basement Sentry

®

II” control box will automatically 

charge the batteries back to full power.  Several hours of recharge time may 

be required before pump can be restarted.

  3.  Complete the final testing of your installation by disconnecting the power to the 

primary pump and removing the power cord from the wall socket. Run water into 

the sump until the DC pump is activated by the float switch. Check pump loop and 

back flow valves for leaks. Check control function as follows:

 

(a)  Red power light is “flashing” (power cord is disconnected from  the 115V 

outlet).

 

(b)  Yellow pump run indicator light is “on” when float switch rises.

 

(c)  Alarm is “on” when float switch rises. (Check alarm “off” switch).

 

(d)  Pump shuts “off” when water level and float switch drops.

 

(e)  Alarm goes “off” when water level and float switch drops.

 

(f)  Yellow pump run indicator light is “on” until reset button has been pushed.

  4.  Reconnect the power cord and your primary pump to the AC wall outlets. The primary 

pump should come on and lower the water level in the sump back to the normal 

operating level and shut off. Both primary and backup system are now ready for use.

Summary of Contents for BASEMENT SENTRY II

Page 1: ...chemicals known to the state of California to cause cancer and birth defects or other reproductive harm 1 Makesurethereisaproperlygrounded115Vreceptacleavailable Do not use primary pump circuit The location must be within 6 of the control box and battery The power supply for your DC control system plugs directly into the 115V outlet Do not use an extension cord 2 Make sure the 115V electrical supp...

Page 2: ...an not be restarted until power is restored and the battery recharged b If power has been restored and water in sump remains high check primary pump Service if required c Acompletelydrainedbatterymayrequire18hoursforafullcharge 7 Alarm sounds during battery recharge cycle a Pushalarmreset max 3times Ifconditionpersists replacebattery Troubleshooting Information Manufacturer warrants to the purchas...

Page 3: ...Deep cycle 12 volt 130 amp hour marine batteries are recommended and will provide approximately 7 hours of continuous pumping time in a sump pump installation with 8 of head pressure In most installations the pump runs intermittently and the battery life is extended accordingly Batteries with top terminals are recommended for ease of installation Pumping time can also be extended by using addition...

Page 4: ...at switch assembly on the lower leg of the discharge outlet tee using the clamp provided see fig 1 and 2 Set tether length to 4 Position pumps in the sump and move float up and down making sure of free movement without interference from any obstructions inside the sump or lid Very shallow sumps may require some adjustment to avoid overfilling or backing up of water into the sump inlet The float sw...

Page 5: ... The 8 3 8 Dimension can be altered to accommodate small basins with min depth of 24 ON LEVEL PRIMARY PUMP END OF PIPE END OF PIPE 7 3 16 PIPE REMOVED OUTLET PUMP PRIMARY BATTERY BOX 8 3 8 5 3 8 1 8 WEEP HOLE 1 8 WEEP HOLE BATTERY BOX PRIMARY PUMP ON LEVEL 7 1 2 5 3 8 8 3 8 END OF PIPE END OF PIPE 7 3 16 PIPE REMOVED PRIMARY PUMP OUTLET ...

Page 6: ...served PUMP LOOP ASSEMBLY FIGURE 3 FIGURE 4 FLOAT SWITCH SK1220 SK957 4 C B A C B A 9 8 5 6 6 7 5 10 1 PUMP LOOP ASSEMBLY BRACKET AND BOTTOM VIEW OF PUMP SUPPLIED BY CUSTOMER DISCHARGE PIPE 1 8 WEEP HOLE 1 8 WEEP HOLE CLAMP PIPE CLAMP 4 TETHER ...

Page 7: ...ICATOR YELLOW PUMP MODE INDICATOR LEAD TO POSITIVE BATTERY TERMINAL LEAD TO NEGATIVE BATTERY TERMINAL FEMALE PLUG FOR PUMP CONNECTION FEMALE PLUG FOR FLOAT SWITCH CONNECTION NONGROUNDED POWER CORD ALARM SILENCE INDICATOR PUMP RUN INDICATOR RED LED YELLOW GREEN LED RED LED YELLOW LED CHARGER RESET LESS THAN 3 SECONDS PUMP TEST GREATER THAN 3 SECONDS TEST SWITCH RED LOW BATTERY INDICATOR ALARM SILEN...

Page 8: ... and the condition of the battery Follow these recommendations Use a B C I size 27 deep cycle battery 175 minute reserve capacity or larger Do NOT use a maintenance free battery unless it is a Gel filled or AGM battery Replace your battery every 3 years Do not let corrosion build up on the battery terminals Do not place your battery on a concrete floor where it will discharge faster To check speci...

Reviews: