background image

6

© Copyright 2010 Zoeller Co. All rights reserved.

Trouble Shooting Guide

A.  UNIT DOESN’T RUN.

B.   PUMP MAKES LOUD NOISES WHEN 

RUNNING.

C.  PUMP RUNS BUT DOES NOT PUMP 

LIQUID OUT.

D.  LIQUID DRAINS BACK INTO PUMP 

FROM DISCHARGE LINE.

E  LIQUID LEAKS FROM AROUND 

CHECK VALVE.

Pump not plugged in.

Low voltage; blown fuse, open circuit.

No condensate in reservoir.

Motor or wiring shorted.

Drain/Discharge line(s) blocked.

Debris in reservoir.

Float bound.

Maximum discharge height exceeded.

Discharge tube blocked.

Check Valve obstruction.

Check Valve damaged.

Check  Valve damaged.

Check Valve obstruction.

Highest point of discharge line is less 
than 5’.

Check Valve is too tight or too loose.

Plug in.

Have a qualifi ed electrician check fuse circuit.

Be certain the appliance is generating con-
 den sate. Check drain line(s) and/or discharge 
line for blockage.

Contact Factory.

Check drain line(s) and/or discharge line for 
block age.

Refer to “Maintenance Guidelines” section for 
clean ing instructions.

Refer to “Maintenance” section for cleaning 
instructions.

Measure from bottom of pump to highest point. 
Rework discharge if height is greater that 18’. 
Refer to STEP 3 for guidelines.

Check discharge line for blockage, remove 
debris.

Refer to “Maintenance” section for cleaning 
in struc tions.

Contact Factory.

Contact Factory.

Refer to “Maintenance” section for cleaning 
instructions. 

Check valve may allow some condensate to 
drain out of line into reservoir. This is normal.

Check valve should be hand tight, then tighten 
an additional 1/2 turn with a 9/16” wrench.

 Condition 

Possible 

Cause 

Remedy

  

Before servicing a pump, always shut off the main pow er 

breaker and then unplug the pump - making sure you are not standing in wa ter 
and are wearing insulated, protective-sole shoes. Under fl ooded  con di tions, 
contact your local electric company or a qualifi ed licensed electrician for 

disconnecting electrical service prior to pump removal. 
If the above checklist does not solve the problem, consult Zoeller Technical Service 
Department 1-(800) 928-PUMP - Do not attempt to service or otherwise dis as -
sem ble  pump.

  5.1)  Testing of Pump (Main Switch)

  1) 

With the discharge line in place, plug in the pump.

  2) 

Pour water into the pump reservoir, through one of the inlets, until the pump activates to verify that the unit 
works.

 

 

5.2)   Testing of Safety Switch (If applicable)

 Note: 

Unplug the pump for this test.

  1) 

Energize the appliance so that it runs.

  2) 

Pour water into the reservoir as described in Section 5.1 item 2.

  3) 

As water rises in the reservoir, the overfl ow Switch should activate, breaking the thermostat circuit to the appli-
ance and/or triggering the alarm.

  4) 

Plug the pump in and allow the pump to empty the tank. As the water level decreases, the appliance and/or the 
alarm will reset.

 STEP 

Testing of Pump Operation 

Summary of Contents for 521

Page 1: ...ch circuit sized according to the National Electrical 1 Inspect all materials Occasionally products are damaged during shipment If the unit is damaged contact your dealer before using 2 Carefully read all the literature provided to familiarize yourself with specific details regarding installation and use before attempting the installation These materials should be retained for future reference 1 C...

Page 2: ...cts etc or other abrasive or corrosive substances Limited Warranty This warranty is in lieu of all other warranties expressed or implied and we do not authorize any representative or other person to assume for us any other liability in connec tion with our products Contact Zoeller Pump Company 3649 Cane Run Road Louisville Kentucky 40211 1961 Attention Customer Service Department to obtain any nee...

Page 3: ... separately protected and properly grounded ground fault protected circuit DO NOT ever cut splice or damage power cord DO Ten Helpful Hints For Easy Installation Do s And Don t s For Installing A Unit NOT carry or lift pump by its power cord DO NOT use an extension cord with this condensate pump 5 DO NOT use a discharge pipe smaller than the pump discharge size 6 DO test pump immediately after ins...

Page 4: ...the furnace drain to the inlet hole s on the pump Refer to Figure 2 2 Figure 1 2 Figure 2 2 Figure 2 1 Note The drain line s should have a continuous downward slope to allow for gravity flow Note Local codes may require the use of a condensate neutralizer when using this pump Note Make sure the drain lines from the A C condenser are supported above the reservoir and no weight from the drain line i...

Page 5: ...low Figure 3 1 SK1764 STEP 3 Installation of Discharge Line STEP 4 Installation of Safety Switch SK1767 4 1 The pump safety switch should be used on 24V Class II control circuits only The pump safety switch connections are available on standard quick connect terminals located on the top cover Two wires with pre crimped connections may be plugged onto the COMMON and RUN terminals and wired into the...

Page 6: ...ntact Factory Refer to Maintenance section for cleaning instructions Check valve may allow some condensate to drain out of line into reservoir This is normal Check valve should be hand tight then tighten an additional 1 2 turn with a 9 16 wrench Condition Possible Cause Remedy Before servicing a pump always shut off the main power breakerandthenunplugthepump makingsureyouarenotstandinginwater anda...

Page 7: ...7 NOTES Copyright 2010 Zoeller Co All rights reserved ...

Page 8: ...IL TO P O BOX 16347 Louisville KY 40256 0347 SHIP TO 3649 Cane Run Road Louisville KY 40211 1961 502 778 2731 1 800 928 PUMP FAX 502 774 3624 www zoeller com Copyright 2010 Zoeller Co All rights reserved ...

Reviews: