H0430700.A - EN - 2014-05
4
EN
Follow the hydraulic connection direction (see § «Dimensions» in the appendix).
The piping must be supported.
•
Connection must use Ø50 PVC rigid pressure piping, from a bypass, on the pool filter circuit, after the filter and before
water treatment.
•
Installing a by-pass is mandatory and facilitates operations on the appliance.
•
Make sure the hydraulic fittings are correctly tightened and that there are no leaks.
Condensate drainage: warning, your appliance can release several litres
of water per day; it is highly recommended to connect the drainage to the
drains.
Connect an interior Ø18 pipe (not supplied), to the corrugated angle to be
fitted under the appliance base (orientable outlet).
1.5 Electric connections
1.5.1 Voltage and protection
•
the heat pump’s power supply must come from a protection and cut-off device (not included) which is compliant with
the country’s applicable standards and regulations,
•
additional protection may be required on installation to guarantee power surge category II,
•
the machine is designed to be connected to a power supply using a neutral TT and TN.S wiring system,
•
electric protection: using a circuit breaker (D curve) or a fuse (calibre 16A see § 1.1), with a separate 30 mA ground fault
circuit breaker (circuit breaker or switch).
•
the electricity supply connection ducting must be static,
•
acceptable voltage variation: ± 6% (when running),
•
use cables suitable for outside use of the H07RN-F type, and of an outer diameter included between 9 and 18
mm,
•
use the cable gland to pass the power supply cable into the appliance.
1.5.2 Connections
•
The electric power supply cable must be isolated from all sharp or hot elements that could damage or crush it.
•
With the power off, check that the power cable is properly connected to the connection terminal
•
Loose terminals can cause the terminal block to heat and lead to the warranty being voided.
•
It is imperative to connect the appliance to an earth rod.
•
Risk of electric shocks inside the appliance.
•
Only a qualified and experienced technician is authorised to wire inside the appliance.
•
If the power supply cable is damaged it should be replaced by a qualified technician.
1.5.3 Remote control panel
The heat pump control panel can be installed at a distance from the appliance. To do this, use the remote control kit
(plastic cover + metal RJ11/RJ45 cable extension, see kit instruction to install).
1.5.4 Connecting options
•
use cables with a cross section of: 2x0.75 mm² at least, of the H07RN-F type, and of an outer diameter included between
8 and 13 mm
Remove the cover (above the cable gland) and install the supplied cable gland to pass the cabling into the
appliance. The options cables and the power supply cable must be supported separately (risk of interference)
using a cable tie inside the appliance just after the cable glands.
Any incorrect connections to terminals 1 to 12 may damage the regulator and void its warranty.
The filtering pump motor should not, under any circumstances, be directly supplied from terminals 11-12.
If there is any intervention on terminals 1 to 12 there is a risk of electric current being returned.
phase (L) + neutral (N) + Ground ( )