Instructions for Installation and Use of the C3100/200/400 Control Panel
31
4.4 DIP Switch Setting (485 Address Setting, Factory
Setting, and Terminal Resistance Setting)
485 address setting
Places 16 of the DIP switch are reserved to set device number for RS485
communication. The code is binary, and the lower places are in the front.
When the switch is set to the
ON
position, it indicates 1 (on); when the switch
is set downwards, it indicates 0 (off).
For example, to set a device number 39=1+2+4+32, which corresponds to the
binary code 111001, put places 1, 2, 3, and 6 to the
ON
position, as illustrated
below.
485 address setting table:
Switch Setting
Place Address
1
2
3
4
5
6
Address No.
1
2
4
16
32
64