Communication solutions for power utilities
1U SHELF TYPE MAS-2
WITH ASYNCHRONOUS PROGRAMMABLE MODEM MAFP - Rev. 9 (January 2018)
7/39
Balance
>60 dB between 420 and 3800 Hz
Insulation voltage
IEC 870-2-1 class 2.
(2)
1 kV
rms
/50 Hz/1 min
Impulse voltage
IEC 870-2-1 class 2.
2 kV
p
(1.2/50
s)
Fast transient bursts
IEC 870-2-1 level 3.
2 kV
p
Damped oscillatory waves
IEC 870-2-1 level 2.
1 kV
p
1.2.3
Receiver
Sensitivity
43 to 0 dBm.
Adjustment in three ranges
Nominal selectivity
for an attenuation of 40 dB
- At 50 Bd/
30 Hz:
192 Hz
- At 100 Bd/
60 Hz:
380 Hz
- At 200 Bd/
120 Hz:
784 Hz
- At 200 Bd/
90 Hz:
560 Hz
- At 200 Bd/
60 Hz:
381 Hz
- At 600 Bd/
180 Hz:
1600 Hz
- At 1200 Bd/
400 Hz: 1472 Hz or 1902 Hz,
depending on whether the modem works in
superimposed band or not.
At 2400 Bd/
800 Hz: 3192 Hz
Figure 3 to Figure 11 show, for each speed
and as an example, the response curve of the
transmission and reception filters at a
determined frequency
(2)
For waves applied between:
- Output terminals and power supply terminals.
- Output terminals and alarm relay terminals.
- Output terminals and ground terminals.