Table 2: Sensing profiles
Profile
Sensitivity
Notes
1
Smoke only - High
Smoke only response, Sensitivity 1
Very high sensitivity
2
Smoke only - Normal
Smoke only response, Sensitivity 2 (std)
Normal sensitivity
3 [1]
Smoke only - Medium
Smoke only response, Sensitivity 3
Medium sensitivity [1]
4
Smoke only - Low
Smoke only response, Sensitivity 4
Low sensitivity
5 [1]
Heat only - High
Heat only response, Sensitivity 1: 58ºC ROR
Standard thermal sensitivity with rate of rise [1]
6
Heat only - Medium
Heat only response, Sensitivity 2: 58ºC FT
Standard thermal sensitivity
7
Heat only - Low
Heat only response, Sensitivity 3: 75ºC ROR
Low thermal sensitivity with rate of rise
8
Heat only- Low Option 2
Heat only response, Sensitivity 4: 75ºC FT
Low thermal sensitivity
9
Smoke High/
Heat Medium
Smoke Sensitivity 1, Heat 1: 58ºC ROR
Early smoke response, Early thermal response
10
Smoke High/
Heat Medium
Smoke Sensitivity 1, Heat 2: 58ºC FT
Early smoke response, Medium thermal response
11
Smoke High/, Heat Low
Smoke Sensitivity 1, Heat 3 - 75ºC ROR
Early smoke response, Low thermal response
12
Smoke High/,
Heat Low Option 2
Smoke Sensitivity 1, Heat 4: 75ºC FT
Early smoke response, Slow thermal response
13
Smoke Normal/
Heat High
Smoke Sensitivity 2, Heat 1: 58ºC ROR
Normal smoke response, Early thermal response
14
Smoke Normal/
Heat Medium
Smoke Sensitivity 2, Heat 2: 58ºC FT
Normal smoke response, Medium thermal response
15
Smoke Normal/
Heat Low
Smoke Sensitivity 2, Heat 3: 75ºC ROR
Normal smoke response, Low thermal response
16
Smoke Normal/
Heat Low Option 2
Smoke Sensitivity 2, Heat 4 : 75ºC FT
Normal smoke response, Slow thermal response
17
Smoke Medium/
Heat High
Smoke Sensitivity 3, Heat 1: 58ºC ROR
Medium smoke response, Early thermal response
18
Smoke Medium/
Heat Medium
Smoke Sensitivity 3, Heat 2: 58ºC FT
Medium smoke response, Medium thermal response
19
Smoke Medium/
Heat Low
Smoke Sensitivity 3, Heat 3: 75ºC ROR
Medium smoke response, Low thermal response
20
Smoke Medium/
Heat Low Option 2
Smoke Sensitivity 3, Heat 4: 75ºC FT
Medium smoke response, Slow thermal response
21
Smoke Low/
Heat High
Smoke Sensitivity 4, Heat 1: 58ºC ROR
Slow smoke response, Early thermal response
22
Smoke Low/
Heat Medium
Smoke Sensitivity 4, Heat 2: 58ºC FT
Slow smoke response, Medium thermal response
23
Smoke Low/Heat Low
Smoke Sensitivity 4, Heat 3: 75ºC ROR
Slow smoke response, Low thermal response
24
Smoke Low/
Heat Low Option 2
Smoke Sensitivity 4, Heat 4: 75ºC FT
Slow smoke response, Slow thermal response
25
Enhanced Clean Room
Dual detector, Smoke Sensitivity High
Heat 58ºC ROR
Verification 5 seconds
Fast smoke response, Fast thermal response
26
Enhanced Normal
Dual detector, Smoke Sensitivity Normal
Heat 58ºC ROR
Verification 20 seconds
Medium smoke response, Medium thermal response
Medium time response
27
Enhanced Industrial
Dual detector, Smoke Sensivity Low
Heat Low sensitivity
Verification 30 seconds
Slow smoke response, Slow thermal response
[1] The ZX832-3 has been certified to comply with 03 and 05 sensing profiles.