background image

P/N 10-4211-501-ZX01-01 • ISS 26JAN15 

 

3 / 4 

Contact information 

For contact information, see www. utcfssecurityproducts.eu.  

Table 2: Sensing profiles 

Profile  

Sensitivity 

Notes 

Smoke only - High 

Smoke only response, Sensitivity 1 

Very high sensitivity 

Smoke only - Normal 

Smoke only response, Sensitivity 2 (std) 

Normal sensitivity 

3 [1] 

Smoke only - Medium 

Smoke only response, Sensitivity 3 

Medium sensitivity [1] 

Smoke only - Low 

Smoke only response, Sensitivity 4 

Low sensitivity 

5 [1] 

Heat only - High 

Heat only response, Sensitivity 1: 58ºC ROR 

Standard thermal sensitivity with rate of rise [1] 

Heat only - Medium 

Heat only response, Sensitivity 2: 58ºC FT 

Standard thermal sensitivity 

Heat only - Low 

Heat only response, Sensitivity 3: 75ºC ROR 

Low thermal sensitivity with rate of rise 

Heat only- Low Option 2 

Heat only response, Sensitivity 4: 75ºC FT 

Low thermal sensitivity 

Smoke High/  
Heat Medium 

Smoke Sensitivity 1, Heat 1: 58ºC ROR 

Early smoke response, Early thermal response 

10 

Smoke High/  
Heat Medium 

Smoke Sensitivity 1, Heat 2: 58ºC FT 

Early smoke response, Medium thermal response 

11 

Smoke High/, Heat Low 

Smoke Sensitivity 1, Heat 3 - 75ºC ROR 

Early smoke response, Low thermal response 

12 

Smoke High/,  
Heat Low Option 2 

Smoke Sensitivity 1, Heat 4: 75ºC FT 

Early smoke response, Slow thermal response 

13 

Smoke Normal/  
Heat High 

Smoke Sensitivity 2, Heat 1: 58ºC ROR 

Normal smoke response, Early thermal response 

14 

Smoke Normal/ 
Heat Medium 

Smoke Sensitivity 2, Heat 2: 58ºC FT 

Normal smoke response, Medium thermal response 

15 

Smoke Normal/  
Heat Low 

Smoke Sensitivity 2, Heat 3: 75ºC ROR 

Normal smoke response, Low thermal response 

16 

Smoke Normal/  
Heat Low Option 2 

Smoke Sensitivity 2, Heat 4 : 75ºC FT 

Normal smoke response, Slow thermal response 

17 

Smoke Medium/ 

Heat High 

Smoke Sensitivity 3, Heat 1: 58ºC ROR 

Medium smoke response, Early thermal response 

18 

Smoke Medium/ 

Heat Medium 

Smoke Sensitivity 3, Heat 2: 58ºC FT 

Medium smoke response, Medium thermal response 

19 

Smoke Medium/ 

Heat Low 

Smoke Sensitivity 3, Heat 3: 75ºC ROR 

Medium smoke response, Low thermal response 

20 

Smoke Medium/ 

Heat Low Option 2 

Smoke Sensitivity 3, Heat 4: 75ºC FT 

Medium smoke response, Slow thermal response 

21 

Smoke Low/ 

Heat High 

Smoke Sensitivity 4, Heat 1: 58ºC ROR 

Slow smoke response, Early thermal response 

22 

Smoke Low/ 
Heat Medium 

Smoke Sensitivity 4, Heat 2: 58ºC FT 

Slow smoke response, Medium thermal response 

23 

Smoke Low/Heat Low 

Smoke Sensitivity 4, Heat 3: 75ºC ROR 

Slow smoke response, Low thermal response 

24 

Smoke Low/ 

Heat Low Option 2 

Smoke Sensitivity 4, Heat 4: 75ºC FT 

Slow smoke response, Slow thermal response 

25 

Enhanced Clean Room 

Dual detector, Smoke Sensitivity High 

Heat 58ºC ROR 

Verification 5 seconds 

Fast smoke response, Fast thermal response 

26 

Enhanced Normal 

Dual detector, Smoke Sensitivity Normal 

Heat 58ºC ROR 

Verification 20 seconds 

Medium smoke response, Medium thermal response 

Medium time response 

27 

Enhanced Industrial 

Dual detector, Smoke Sensivity Low 

Heat Low sensitivity 

Verification 30 seconds 

Slow smoke response, Slow thermal response 

[1] The ZX832-3 has been certified to comply with 03 and 05 sensing profiles. 