SURVEYOR
DEVICE
LOCAL - REMOTE
PASS / FAIL
SIGNAL QUALITY %
REMOTE - LOCAL
BATTERY
Whether undertaking a Ziton RLM or Ziton Hub/RCC survey, a level of 24dB or above is
required as a pass result.
>45dB >45dB Pass
BG = 0dB
>45dB >45dB Pass
100% 98% 0001
Incoming
signal level
in dB
Background
Level in dB
Outgoing
signal
level in dB
Pass / Fail
result
Surveyor
Battery
level
Device
Battery
level
Number of
tests
conducted
Alternating to
Incoming
signal
success rate
Outgoing
signal
success rate
Using the Device Survey Tool
SURVEYOR
DEVICE
LOCAL - REMOTE
PASS / FAIL
SIGNAL QUALITY %
REMOTE - LOCAL
BATTERY
>45dB >45dB Pass
BG = 0dB
With the Device Survey Tool switched on, depress the rear switch to initiate a signal. After a few
seconds results will be displayed and a high pass or a flat fail tone will be heard.
LED signal indication is also shown on the device, a Green LED indicates a Pass and the Yellow
LED indicates a Fail.
Note; the battery icons shown above (bottom right of
display), will alternate with a test number also shown.
The background levels are taken into account prior to displaying the events on the units. If the
required device position fails to pass the test then a further RLM/RCC position will need to be
found closer to the device and the survey repeated. Every device position should be recorded
along with the received signal levels.
Survey Results Explained
The figures shown are explained as follows:-
>21dB >21dB Fail
BG = 7dB
>45dB >45dB Pass
BG = 0dB
Summary of Contents for ZR4ST-3
Page 3: ...Start www acornfiresecurity com www acornfiresecurity com...
Page 5: ...About The Survey Kit www acornfiresecurity com www acornfiresecurity com...
Page 10: ...RLM Survey www acornfiresecurity com www acornfiresecurity com...
Page 16: ...Hub RCC Survey www acornfiresecurity com www acornfiresecurity com...