Ziton ZP755W-2R Installation Sheet Download Page 3

© 2014 UTC Fire & Security. All rights reserved. 

3 / 4 

P/N 501-1786ZE-1-08 • REV 08 • ISS 30JAN14  

Table 2: Tone settings 

SW2-6 device mode 
switch setting 

Device mode 

SW2 switch setting 
-1 -2 -3 

Mapping input type 

Fast flash 

Steady 

Tone type 

Tone A primary/alert 

Tone B secondary/evac 

OFF 

ZP755  

 

Intermittent 

Continuous 

OFF 

ZP755 

 

Continuous 

Intermittent 

OFF 

ZP755 

 

Continuous 

Two-tone 

OFF 

ZP755 

 

Two-tone 

Continuous 

OFF 

ZP755 

 

Two-tone 

Intermittent 

OFF 

ZP755 

 

Intermittent 

Two-tone 

OFF 

ZP755 

 

Not used 

 

ON 

ZP754 

 

Intermittent 

Continuous 

 

Setting the volume 

The sounder has a volume control potentiometer to adjust the 

volume. Refer to Figure 5. 

WARNING: 

To conform to EN 54 Part 3 sound output levels, 

the volume control pot 

must 

be set to the full clockwise 

position. If the volume is adjusted for any reason, it 

must 

be 

returned to the full clockwise position. 

Figure 5: Volume control 

1

2

3

3050-01

1

2

3

4

 

1.  Tone Select 

2.  SW2-6 on 

3.  SW2-6 off 

4.  Volume control  

Mounting the sounder  

To mount the sounder: 

1.  Insert four M4 × 25 mm screws through the PCB mounting 

holes, and then secure to the backbox surface. See 

Figure 6. 

2.  Install the sound output assembly into the backbox, and 

then secure using mounting screws. 

Figure 6: Mounting 

3064-01

1

2

3

4

 

1.  M4 × 25 mm screws 

2.  Mounting screws 

3.  Sound output assembly 

4.  PCB  

Sounders per loop 

The sounder can be powered directly from the loop of a ZP3 

panel. Use Table 3, in conjunction with Figure 7, to determine 

the quantity of detectors and sounders that can be connected 

to a two-core shielded loop. 

Figure 7: Detector/sounders per loop 

 