P/N 501-1786ZE-1-08 • REV 08 • ISS 30JAN14
Figure 3: Address switch setting
Mode and tone settings
The sounder includes a seven-segment DIP switch (SW2)
used to select operating mode, device mode, and tone. See
Figure 4.
Figure 4: Mode of operation switch settings
1
2
3
4
5
1. Power selection jumpers
2. SW2 configuration switch
3. Tone setting
4. Device mode
5. Operating mode
Setting the operating mode
The device operates as a dedicated (stand-alone) sounder with
its own unique loop address when SW2-7 is set to ON.
To configure operation as a stand-alone sounder:
1. Set SW2-7 to ON.
2. Navigate to the following menu to tag the sounders as
SAB:
ZP3 Panel Menu/Setup/Sounders/SAB/Add SAB
The Planner can also be used.
3. To map an alert-to-evac function, make the first input type
a fast flash input.
The sounder will sound the alert tone in response to a fast
flash input or an evac tone when the input configured as
steady is triggered, overriding the alert tone.
Setting the device mode
SW2-6 selects whether the loop sounder operates in ZP755
mode or in ZP754 emulation mode as described in Table 1.
Table 1: SW2-6 mode selection switch
Mode
SW2-6
Output signal
Requirement
ZP755
OFF
User-selectable two-
tone operation and
full monitoring
ZP3 software
v1.18 or later
ZP754
emulation
ON
Two fixed tones
ZP5 panels or
ZP3 panels with
legacy software
Setting the tone
Two different tones can be programmed to operate from the
panel. In ZP755 mode these tones are selected using SW2-1,
SW2-2, and SW2-3. Refer to Table 2.
Note:
In the ZP panel I/O mapping menu, outputs are
programmed as "steady" or "flashing." The link to the table
below is as follows:
•
Tone A = Panel setting "fast flash/slow flash.”
•
Tone B = Panel setting "steady.”