background image

 

ZP755HA-2 Addressable Omnidirectional 
Sounder Installation Sheet 

 

Description 

The ZP755HA-2 is an addressable, omnidirectional horn 
sounder, designed for use on Ziton analogue addressable fire 
detection and alarm systems.  

The device includes a volume control, an address-setting 
switch, programmable tone settings, and a pair of jumpers to 
select the operating power — from the analogue addressable 
loop or an external supply. The sounder plugs into a base that 
is purchased separately. See Table 1 for a list of model 
numbers. 

Table 1: Models 

Model number 

Description 

Sounder: 
 

ZP755HA-2R 

 

ZP755HA-2P 

 
Addressable, horn sounder, Red 
Addressable, horn sounder, Polar white 

Base: 
 

SPB-2R 

 

SPB-2P 

 
Plug in-base, Red 
Plug in-base, Polar White 

Installation 

To install the device follow these general steps. 

1.  Wire the base. 
2.  Set the operating power. 
3.  Set the address. 
4.  Set the mode of operation. 
5.  Set the tone. 
6.  Set the volume. 
7.  Mount the sounder onto the base. 

The details of each step are given below. 

Wiring the base 

Connect the loop wiring for the plug-in base as shown in 
Figure 1. There is no wiring between the sounder and plug-in 
base. 

Figure 1: Loop wiring for the plug-in base 

 

1. 

Ext. 24 VDC+ IN/OUT  

2. 

Ext. 24 VDC ground IN/OUT 

5. 

Loop+ IN/OUT 

6. 

Loop − IN/OUT 

7. 

Shield 

 

Setting the operating power 

The sounder includes a pair of power selection jumpers, J1 
and J2. To select the source of the sounder operating power, 
position the jumpers as shown in Figure 2. 

Figure 2: Power-selection jumper configuration 

 

1. 

Loop powered 

 

2. 

External 24 VDC 

Note: 

When using an external power supply, use only one that 

is CE and EN 54-4 compliant to power all the sounders on the 
same loop. 

 

6

2

5

1

J1

J1

J2

J2

2

1

www.acornfiresecurity.com

www.acornfiresecurity.com

Reviews: