background image

Installation Sheet 

No.: 1776 iss 03 

ZP755HA-2 Addressable Omni-directional Sounder 

Installation sheet 

501-1776ZE-1-03 

ZP755HA-2 Addressable Omni-directional Sounder 

Page 2 

14/11/2006 

 

 
Operating voltage: 

External supply – 16 to 30 VDC 

 

Loop supply – ZP protocol 19.5 - 
20.5 V pulsed, max. 4 V line loss 

Current (RMS)-quiescent:  820 µA 
Current alarm (RMS): 

6.4 mA 

Current alarm (max. avg. 
- excl. device address): 

9.4 mA 

Max number: 

50 per 1 km loop (subject to 
cable size and sounder spacing) 

Environmental 
Application: 

Indoor use 

EN60529 rating: 

IP50 

Temp. range: 

-10 to 70 °C 

Humidity range: 

10% to 95% RH (non-condensing) 

EMC: 

CPD compliant 

Construction 
Material: 

Moulded thermoplastic 

Dimensions (

 x D): 

127 x 113 mm 

Colour: 

White or red 

Weight: 

275 g 

Physical Installation 

Connecting Wiring 

Loop  wiring  for  the  plug-in  base.  There  is  no  wiring 
between the sounder and plug-in base. See Figure 1 
in  the  adjacent  column.  Plug-in  base  supplied 
separately. 

 

 

Figure 1 

Mounting the Sounder 

Align  the  addressable  sounder  to  the  plug-in  base. 
Push up (step 1) and turn the sounder until it clicks 
into place (step 2). Push the sounder up once more 
to engage (step 3). See Figure 2 below. 

 

Figure 2 