4 / 4
P/N 501-1789ZE-1-10 • REV 10 • ISS 16APR14
Sounders per loop
The sounder can be powered directly from the loop of Ziton control
panels. Use Table 5 Tone settings, in conjunction with Figure 6, to
determine the quantity of detectors and sounders that can be
connected to a two-core shielded loop when loop powered.
Figure 6: Detector/sounders per loop
A.
Cable length panel to first sounder
B.
Cable length first to last sounder
C.
Cable length last sounder to panel
1.
Detectors and Sounders
Table 7: Maximum detectors and sounders per loop
A
B
C
Quantity allowed [1]
10 m
980 m
10 m
60 detectors and 35 sounders
90 detectors and 30 sounders
100 m
800 m
100 m
50 detectors and 35 sounders
90 detectors and 30 sounders
200 m
600 m
200 m
40 detectors and 35 sounders
90 detectors and 30 sounders
300 m
400 m
300 m
40 detectors and 30 sounders
90 detectors and 25 sounders
[1] Using a two-core shielded loop of 1000 meters cable size 1.5 mm²
Specifications
Operating voltage
External supply
Loop supply, ZP protocol
18 to 30 VDC
19.5 to 20.5 V pulsed, max. 4 V line loss
Current (line powered)
Quiescent (RMS)
Alarm (RMS)
Alarm (excluding device
address)
Alarm (at device address)
500
µ
A
6 mA
14 mA max.
14 mA max.
Current (externally powered)
Quiescent (RMS)
Alarm (RMS)
Maximum number
470
µ
A
500
µ
A
35 per 1 km loop (subject to cable size and
sounder spacing)
Strobe
Frequency
Light output
Flash rate 1.1 seconds
Less than 1J xenon element
Tones
See Table 5 Tone settings.
See Table 6 Tones.
Sound distribution
Wide
Measured anechoic sound levels
See Figure 7
Monitoring
Operating power level
Sound output level
Tested continuously
Self test facility
Compatibility
Ziton analogue addressable systems
Addressing method
7-segment DIP switch
Mounting
Surface, with base
Wiring
Two-core loop
Construction
Material
Weight
Dimensions (Ø × D)
Moulded thermoplastic
156 g
127 × 47 mm incl. base
Operating environment
Temperature
Relative humidity
−10 to +60°C
10 to 95%, noncondensing
Storage temperature
−20 to +70°C
Figure 7: Measured anechoic sound levels
Note:
These measurements correspond to the highest level for the EN 54-
3 compliant tones of UK-continuous, UK intermittent, and UK-two-tone
.
Regulatory information
This section includes both regulatory information and a summary on
the declared performance according to the Construction Products
Regulation 305/2011. For detailed information refer to the product
Declaration of Performance.
Certification
Certification body
0370
Declaration of
Performance number
360-5202-0199
Year of first CE
marking
14
Product Identification
ZP755BV-4P
Intended use
See DoP point 3
Essential
characteristics
See DoP point 9
Manufacturer
Gulf Security Technology Co.,Ltd
80, Changjiang East Road,
QETDZ, Qinhuangdao, Hebei Province, China 066004
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
European Union
directives
1999/5/EC (R&TTE directive): Hereby, UTC Fire &
Security declares that this device is in compliance with
the essential requirements and other relevant provisions
of Directive 1999/5/EC.
2002/96/EC (WEEE directive): Products marked with this
symbol cannot be disposed of as unsorted municipal
waste in the European Union. For proper recycling,
return this product to your local supplier upon the
purchase of equivalent new equipment, or dispose of it
at designated collection points. For more information
see: www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.
1
6
5
O
105
O
75
O
45
O
1
5
O
13
5
O
dBA
65
70
75
80
85
65
70
75
80
85