background image

4 / 4 

 

P/N 501-1789ZE-1-10 • REV 10 • ISS 16APR14  

Sounders per loop 

The sounder can be powered directly from the loop of Ziton control 
panels. Use Table 5 Tone settings, in conjunction with Figure 6, to 
determine the quantity of detectors and sounders that can be 
connected to a two-core shielded loop when loop powered. 

Figure 6: Detector/sounders per loop 

 

A. 

Cable length panel to first sounder 

B. 

Cable length first to last sounder 

C. 

Cable length last sounder to panel 

1. 

Detectors and Sounders 

 

Table 7: Maximum detectors and sounders per loop 

Quantity allowed [1] 

10 m 

980 m 

10 m 

60 detectors and 35 sounders 
90 detectors and 30 sounders 

100 m  

800 m 

100 m 

50 detectors and 35 sounders 
90 detectors and 30 sounders 

200 m 

600 m 

200 m 

40 detectors and 35 sounders 
90 detectors and 30 sounders 

300 m  

400 m  

300 m 

40 detectors and 30 sounders 
90 detectors and 25 sounders 

[1] Using a two-core shielded loop of 1000 meters cable size 1.5 mm² 

Specifications 

 

Operating voltage 

 

External supply 

 

Loop supply, ZP protocol 

 

18 to 30 VDC 

19.5 to 20.5 V pulsed, max. 4 V line loss 

Current (line powered) 

 

Quiescent (RMS) 

 

Alarm (RMS) 

 

Alarm (excluding device 

 

address) 

 

Alarm (at device address) 

 

500 

µ

6 mA 

14 mA max. 

 

14 mA max. 

Current (externally powered) 

 

Quiescent (RMS) 

 

Alarm (RMS) 

 

Maximum number 

 

470 

µ

500 

µ

35 per 1 km loop (subject to cable size and 

sounder spacing)  

Strobe 

 

Frequency 

 

Light output 

 

Flash rate 1.1 seconds 

Less than 1J xenon element 

Tones 

See Table 5 Tone settings. 

See Table 6 Tones. 

Sound distribution 

Wide 

Measured anechoic sound levels 

See Figure 7 

Monitoring 

 

Operating power level 

 

Sound output level 

 

Tested continuously 

Self test facility 

Compatibility 

Ziton analogue addressable systems 

Addressing method 

7-segment DIP switch 

Mounting 

Surface, with base 

Wiring 

Two-core loop 

Construction 

 

Material 

 

Weight 

 

Dimensions (Ø × D) 

 

Moulded thermoplastic 

156 g 

127 × 47 mm incl. base 

Operating environment

 

Temperature 

 

Relative humidity 

 
−10 to +60°C 
10 to 95%, noncondensing 

Storage temperature 

−20 to +70°C 

Figure 7: Measured anechoic sound levels 

 

Note: 

These measurements correspond to the highest level for the EN 54-

3 compliant tones of UK-continuous, UK intermittent, and UK-two-tone

 
Regulatory information 

This section includes both regulatory information and a summary on 
the declared performance according to the Construction Products 
Regulation 305/2011. For detailed information refer to the product 
Declaration of Performance. 
 

Certification 

 

Certification body 

0370 

Declaration of 

Performance number 

360-5202-0199 

Year of first CE 

marking 

14 

Product Identification 

ZP755BV-4P 

Intended use 

See DoP point 3 

Essential 

characteristics 

See DoP point 9 

Manufacturer 

Gulf Security Technology Co.,Ltd 

80, Changjiang East Road, 

QETDZ, Qinhuangdao, Hebei Province, China 066004 

Authorized EU manufacturing representative:  

UTC Fire & Security B.V.  

Kelvinstraat 7, 6003 DH Weert, Netherlands 

European Union 

directives 

1999/5/EC (R&TTE directive): Hereby, UTC Fire & 

Security declares that this device is in compliance with 

the essential requirements and other relevant provisions 

of Directive 1999/5/EC. 

 

2002/96/EC (WEEE directive): Products marked with this 

symbol cannot be disposed of as unsorted municipal 

waste in the European Union. For proper recycling, 

return this product to your local supplier upon the 

purchase of equivalent new equipment, or dispose of it 

at designated collection points. For more information 

see: www.recyclethis.info. 

 

Contact information 

For contact information, see www.utcfssecurityproducts.eu. 

1

6

5

O

105

O

75

O

45

O

1

5

O

13

5

O

dBA

65

70

75

80

85

65

70

75

80

85