Chapter 3: Commissioning
ZP3-ECU Extinguishing Control Unit Installation and Commissioning Manual
19
Addressing
The ECU uses two addresses on the addressable loop. These are configured
using the Extinguishing Relay and Relay DIP switches on the ECU main board
Figure 8: DIP switch locations on the ECU main board
Any two addresses may be used but the two addresses must be at least twenty
apart as security against short-term random noise interference.
The fire alarm control panel identifies the extinguishing relay address as an
extinguishing unit. The switches are numbered 1 to 7 and may be configured to
represent addresses from 1 to 127.
A switch represents a particular value when ON (an OFF switch represents 0).
To configure the address of a device, add the switch values for all the switches
which are ON. Note that the DIP switch number is not the DIP switch value – see
Figure 9: DIP switch values and address example