ZP2-A Series Operation Manual
13
Icon
Description
Manual call point alarm
(sprinkler) [1]
This icon indicates a manual call point alarm
(sprinkler).
Manual call point alarm
(“hausalarm”) [1]
This icon indicates a manual call point alarm
(“hausalarm”). This is a local alarm with no fire routing
activation.
[1] These icons appear in the message display area with the notification details.
[2] A maximum limit of 512 events applies to each type of reported event. If one or more event
type exceeds the maximum limit, then a System Fault is indicated. See “System Fault LED
indication – maximum limit for event type reporting” on page 10 for more information.
Indication of remote and local events on the LCD
The local control panel ID is always displayed on the LCD (see Figure 3 on page
11).
If your control panel forms part of a fire network, the event notification includes
the panel ID reporting the event as follows:
• If the panel ID matches the local ID, then the event relates to the local control
panel.
• If the panel ID does not match the local ID, then the event is reported by the
remote control panel with the panel ID indicated.
Acoustic indicators
The control panel uses the following acoustic indicators to highlight system
events.
Caution:
The information in the table below describes the default buzzer
configuration – the installer may have configured your control panel so that the
buzzer does not activate for some event types.
Table 8: Control panel acoustic indicators
Indication
Description
The buzzer sounds continuously
Indicates a fire alarm or a system fault
The buzzer sounds intermittently (long tone) [1] Indicates all other faults
The buzzer sounds intermittently (short tone) [1] Indicates a condition
[1] A long tone is 50% ON and 50% OFF. A short tone is 25% ON and 75% OFF.