Item
Control/LED
LED colour Description
12
Reserved for future
use
This LED-switch position is reserved for future
use.
13
Expansion I/O
Fault/Disabled LED
Yellow
Indicates that an installed expansion board has a
fault or is disabled. Expansion boards are
optional.
A flashing LED indicates a fault. A steady LED
indicates a disablement.
Consult your system installer to determine
whether your system has expansion modules
installed.
14
General Disable
button and LED
Yellow
Disables a system feature or device (when
pressed with the corresponding button).
The disablement of some devices requires
pressing the button for more than 3 seconds.
(See “Disabling other extinguishing devices” on
page 25 for further details.)
A steady General Disable LED and the
corresponding feature or device yellow LED
indicates a disablement.
15
General Test button
and LED
Yellow
Tests a system feature or device (when pressed
with the corresponding button).
Testing of some devices requires pressing the
button for more than 3 seconds. (See “Testing
other extinguishing devices” on page 26 for
further details.)
A steady General Test LED and the
corresponding feature or device yellow LED
indicates a test.
16
Low Pressure LEDs Yellow
Indicates the pressure status of the extinguishing
agent container.
A flashing upper LED indicates that the pressure
in the extinguishing agent container is low (the
General Fault LED also flashes).
A flashing lower LED indicates an open or short
circuit wiring fault. A steady yellow LED indicates
a disablement or test.
17
Extinguishing Agent
Flow LEDs
Red/Yellow
Indicates the extinguishing agent flow status.
A steady red LED indicates that the extinguishing
agent was released out of its container and into
the extinguishing area.
A flashing yellow LED indicates an open or short
circuit wiring fault. A steady yellow LED indicates
a disablement or test.