0x1007

ENUM8
reportable

ModeAfterDry

The mode after Dry Mode:
Value=0 : OFF
Value=1 : Manual mode
Value=2 : Auto mode –schedule (default)
Value=3 : Away mode

0x1224

0x1008

ENUM8
reportable

TemperatureDisplay : 

Value=0 : Room Temp (Default)
Value=1 : Floor Temp

0x1224

0x1009

INT8U
reportable

WindowOpenCheck

The threshold to detect open window, range is 0.3-8, unit is 
0.5ºC,
0 means disabled, default is 0

0x1224

0x100A

INT8U
reportable

Hysterersis

Hysterersis setting, range is 5-20, unit is 0.1ºC, default value 
is 5

0x1224

0x2001

INT8U,
reportable

AlarmAirTempOverValue

Room temp alarm threshold, range is 0.20-60, unit is 1ºC,
0 means disabled, default is 45

0x1224

Command supported:

Command

Description

0x0000

Setpoint Raise/Lower

Increase or decrease the set temperature according to current mode, unit is 
0.1ºC

5.2.5 Simple Meter-0x0702 (Server)

Attributes supported:

Attribute

Type

Description

0x0000

unsigned48 ,
read-only,
reportable 

CurrentSummationDelivered 

Indicates the current amount of electrical energy delivered to the load.

0x0200

bitmap8 ,
read-only

Status

Flags indicating current device status,  always is 0x00

0x0300

enum8 ,
read-only

UnitOfMeasure

The unit of metering data, this is always kWh(0x00)

0x0303

map8 ,
read-only

SummationFormatting

The decimal point on the left and right sides of the data, this is always  0x00

0x0306

bitmap8,
read-only

MeteringDeviceType

Metering data type, this is always Electric Metering (0x00)

5.2.6 Electrical Measurement-0x0b04(Server)

Attributes supported:

Attribute

Type

Description

0x0000

bitmap32 ,
read-only

MeasurementType 

Indicates the physical entities that this devices is able to measure. Supports 
only bit0: Active measurement (AC) 

0x0505

int16U ,
read-only,
reportable 

RMSVoltage

Single phase valid voltage, unit is V

0x0508

int16U ,
reportable,
read-only

RMSCurrent

Single phase valid current, unit is A

0x050B

int16S ,
reportable
read-only

ActivePower 

Single phase valid power, unit is W

0x0600

int16U,
read-only

ACVoltageMultiplier

0x0601

int16U,
read-only

ACVoltageDivisor

Used together with above attributes, the real displayed voltage = 
RMSVoltage* ACVoltageMultiplier
/ ACVoltageDivisor

0x0602

int16U,
read-only

ACCurrentMultiplier

0x0603

int16U,
read-only

ACCurrentDivisor

Used together with above attributes, the real displayed current = RMSCurrent 
* ACCurrentMultiplier
/ ACCurrentDivisor

0x0800

int16U,

ACAlarmsMask

Specifies which configurable alarms may be generated, only
Bit1: Current Overload is set, if set=0, then ACCurrentOverload=0, over 
current will not be detected

0x0802

int16S ,
reportable
read-only

ACCurrentOverload

Alarms when the current is over a certain value,  0, 10-16, unit is A

Proprietary Attributes:

Attribute

0x0000

Type

Int8u,
reportable

Manufacturer code

0x1224

Description

OverCurrent 

Over current value set by the user, range is 0, 10-16, 
ACCurrentOverload will change spontaneously if this 
value is modified. 

5.2.7 Alarm-0x0009(Server)

Please set a valid value for ACAlarmsMask of Electrical Measurement.
The Alarm Server cluster can generate the following commands

CmdID

Description

0x00

Alarm:

The alarm code of Electrical Measurement is 0, 
Proprietary command, 

Manufacturer code=0x1224

CmdID

Description

0x00

Room air temperature over heat, not alarm code

0x2002

ENUM8
reportable

Away Mode Set:

Value=0: not away (default)
Value=1: away

0x1224

0x1006

INT8U
reportable 

DryTime

The duration of Dry Mode, range is 5-100, unit is min.
Default value is 5.

0x1224

0x1005

INT8S,
reportable

FloorSenserCalibration

The temp compensation for the external (floor) sensor, range 
is -30-30, unit is 0.1°C. default value 0

0x1224

Summary of Contents for ROB-200-040-0

Page 1: ...EMC RF EN IEC 61000 3 2 2019 EN 61000 3 3 2013 A1 2019 EN 60730 1 2016 A1 2019 EN 60730 2 19 2019 A1 2019 A2 2020 EN 50663 2017 ETSI EN 301 489 1V2 2 3 ETSI EN301 489 3V2 1 1 ETSI EN300 220 1 v3 1 1...

Page 2: ...1 Switch Operation modes Short press button on Home interface to switch operation modes the icons of Away Manual Comfort Automatic Energy Save Drying OFF modes will be displayed alternatively for 3 s...

Page 3: ...x2001 of Thermostat Cluster 0x0201 when this value is set as 0 this function is disabled Over heat alarm interface is as follow Note to cancel over current alarm or over heat alarm just press and hold...

Page 4: ...ribute TemperatureDisplay 0x1008 of Thermostat Cluster 0x0201 Operate Brightness Mid Level by default The OLED display brightness when operate the device Adding to a Zigbee Network Operate your Zigbee...

Page 5: ...server Scenes Allows storing one or more scenes per group where each scene consists of a pre set on off state value You may either store the current values as a scene or provide scene settings when ad...

Page 6: ...format allows 0 1 C Default value 0 0x0011 int16S reportable OccupiedCoolingSetpoint This system is not invalid 0x0012 int16S reportable OccupiedHeatingSetpoint Range is 0 4000 the maximum resolution...

Page 7: ...16U read only reportable RMSVoltage Single phase valid voltage unit is V 0x0508 int16U reportable read only RMSCurrent Single phase valid current unit is A 0x050B int16S reportable read only ActivePow...

Page 8: ...executed when away mode is selected Check whether away mode time is set as 0 or within valid time range 4 Over heat alarm when power on the device Possible reason the set sensor type is not correct o...

Reviews: