UFR1001E
12420-0701-08
Page
27 / 45
www.ziehl.de
10.
Technical Data
Control voltage Us:
Rated connection
AC/DC 24-270 V, 0/40...70 Hz, < 5 VA
DC: 20.4...297 V, AC: 20.4...297 V
Output relay:
2 x change-over contact
Switching voltage
Max. AC 440 V
Conventional thermal current Ith
6 A
Inrush current (at 10 % ED)
25 A max. 4 s / 50 A max. 1 s
Nominal operating current Ie (AC 15)
6 A AC 250 V
Recommended series fuse
gG/gL 6 A
Contact service life, mech.
30 x 10
6
switching cycles
Contact service life, electr.
1 x 10
6
operating cycles at AC 250 V / 6 A
2 x 10
5
Voltage measurement:
Measurement voltage phase phase
Adjustment range phase phase
Measurement voltage phase N
Adjustment range phase N
Measurement principle
Real root mean square measurement both half waves
Hysteresis
Adjustable
Measurement error (with N)
± 0.6 % of the measurement value
Measurement error (without N)
± 0.8 % of the measurement value
Display accuracy
>100V: -1 digit (res. 1 V), <100V: -1 digit (res. 0.1V)
Measurement function
3-phase with/without N
Response time
Adjustable
Reset time
Input resistance Phase-N
Frequency measurement
Frequency range
Hz
Adjustment range
Hysteresis
Measurement accuracy
± 0.04Hz ± 1 digit
Response time
Adjustable
Reset time
Vector surge
Measurement range
Adjustment range
Response time
< 50 ms
Reset time
Delay at Us on
ROCOF (df/dt)
Frequency range
Hz
Adjustmet range
0,100
0
Hysteresis
fixed 0,05Hz
Measurement error
± 0,04Hz ± 1Digit
Response time
Reset time
adjustable 0 (>200ms)
Measurement time
Number of adjusted Periods * Periods du Response
time
Summary of Contents for UFR1001E
Page 31: ...UFR1001E 12420 0701 08 Page 31 45 www ziehl de 14 Certificate of conformity VDE AR N 4105 ...
Page 32: ...UFR1001E 12420 0701 08 Page 32 45 www ziehl de ...
Page 33: ...UFR1001E 12420 0701 08 Page 33 45 www ziehl de 15 Certificate of conformity bdew 2008 2013 ...
Page 34: ...UFR1001E 12420 0701 08 Page 34 45 www ziehl de ...
Page 35: ...UFR1001E 12420 0701 08 Page 35 45 www ziehl de ...
Page 36: ...UFR1001E 12420 0701 08 Page 36 45 www ziehl de ...
Page 37: ...UFR1001E 12420 0701 08 Page 37 45 www ziehl de ...
Page 38: ...UFR1001E 12420 0701 08 Page 38 45 www ziehl de ...
Page 39: ...UFR1001E 12420 0701 08 Page 39 45 www ziehl de ...
Page 41: ...UFR1001E 12420 0701 08 Page 41 45 www ziehl de 17 Certificate of conformity GB G59 3 Pr 20 21 ...
Page 42: ...UFR1001E 12420 0701 08 Page 42 45 www ziehl de 18 Certificate of conformity GB G83 2 Pr 22 23 ...