TR250
12410-0701-03
Page
10 / 18
www.ziehl.de
8
Installation
The unit can be installed as follows:
Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715
With screws M4 for installation on walls or panel. (additional latch included in delivery)
Connection according to connection plan or type plate.
A circuit-breaker or switch must be situated within easy reach of the
unit and fused. Installation excess current protection should be ≤ 10 A.
9
Putting into operation
9.1 Display Mode
Indication of the actual temperature of the warmest sensor. LEDs (yellow) show, which sensor or group of
sensors is selected. Change with Set
►.
Indication of the stored minimum- resp. maximum-value: Press up
▲ or down ▼ for 2 s. Reset min/max with
Reset
► for 2 s.
Leave Display Mode with buttons
▲/▼.
Sensors type Pt ... resp. KTY ..:
indication of temperature in °C (optional °F)
Sensor type PTC (thermistor):
indication of resistance of sensor in kΩ
LEDs Sensor in Display Mode
ON
Value of this sensor is being displayed
Flash
Sensor Error
2 or more LEDs Sensor ON
warmest of those sensors in display
Alternating illumination
All sensor values are displayed for 2s each consecutively
LEDs Alarm in Display Mode
OFF
Switching point not exceeded
ON
Switching point exceeded, relay switches
Flash
Switching delay time dAL runs
Flash
Switching back delay time doF runs.
Flash
Ready for Reset, switching interlocked.
Reset by button RESET
► or closing of a contact at terminals Y1-Y2.
A continuously closed contact at Y1-
Y2 doesn’t result in a reset.
During periodical relay-test the appropriate LED lights up.
9.2 Programming Mode
Programming of sensors 1-3 (
S1/S2/S3
):
Select menu item with
▲/▼until
S1
and type of sensor are alternating in the display, e.g.
S1/100
for Pt 100.
Here it can be clearly read out, which type of sensor is selected and which alarms are affected by this
sensor (red LED Alarm on).
Enter into programming with Set
►.
Select type of sensor with
▲/▼ (
diF
can be selected at
S3
, if
S1
and/or
S2
are not
PtC
. with
S3
=
diF
it is handled as difference sensor 2 minus sensor 1).
Compensate line-resistance (enter value of resistance of line) or select 3-wire or
nc
(not connected,
if no sensor is connected to this input). At setting
PtC
no compensation of line-resistance is
necessary/possible.