TR111V
12090-0703-02
Page
6 / 8
www.ziehl.de
10
Technical data
Rated supply voltage Us
DC/AC 24
– 240 V
0/50/60 Hz
Tolerance
DC 20.4 - 297 V
AC 20 - 264 V
Power consumption
< 1.5 W
< 5 VA
Output relay K1
1 change over contact
Switching voltage
max. AC 300 V; DC 300 V
min. voltage / current
12 V 10 mA
conventional thermal current Ith
max. 3 A
Switching power
max. AC cos φ = 1
750 VA (250 V * 3 A)
Contact life electrical
2 x 10
5
operating cycles AC 250 V / 3 A
5 x 10
5
operating cycles AC 250 V / 2 A
1 x 10
6
operating cycles AC 250 V / 0,8 A
Utilization category
Rated operational current
AC-15
Ie = 2 A
Ue = 250 V
Rated operational voltage
DC-13
Ie = 2
Ue = 24 V
DC-13
Ie = 0,8 A Ue = 60 V
DC-13
Ie = 0,4 A Ue = 120 V
DC-13
Ie = 0,2 A Ue = 240 V
Sensor connection
Pt100 (RTD) according to EN60751
Sensor voltage
< 5 V
Sensor current
< 2,5 mA
Short circuit
< 15 Ω
Type of connection
3-
wire, max resistance 3x 25 Ω
Limti value
Measuring- ranges
3 or 4 ranges selectable
3 measuring- ranges
-
10…40 °C / 0…100 °C / 0…200 °C
Repeat error
app. 1 K
4 measuring- ranges
0…100 °C / 100…200 °C / 200…300 °C /
300…400 °C
Repeat error
app. 1,6 K
Error of setting
± 5 K
Temperature- dependence
≤0,05 %/K
Hysteresis
Adjustable app. 2…10 K
Switching delay d
on
/d
off
Adjustable 0,1…10 s
Testing conditions
EN 61010-1
Rated impulse withstand voltage
4000 V
Overvoltage category
III
Pollution degree
2
Rated insulation voltage Ui
300 V
On period
100 %
EMC-Tests
EN 61326-1 industrial environment
emission
EN 61326-1; CISPR 11 class B
immunity
EN 61326-1 industrial environment
Electrical fast transient / Burst
EN 61000-4-4 ±4 kV
Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms
SURGE
IEC 61000-4-5 ±2 kV
Electrostatic discharge
IEC 61000-4-2 ± 6 kV contact discharge, ± 8 kV air
discharge