Overview of functions 

  Pt100-input 2- or 3-

wire automatic compensation of line up to 500 Ω total resistance ( line) 

  Detection of sensor-break 

  Easy adjustment of Zero and Full-scale by pressing a button 

  Wide measuring-range -200... +850 °C 

  LEDs for display of operative state 

  Analog output 0 ... 20 mA / 4 ... 20 mA.  Analog output 0 ... 10 V 

  Housing for DIN-rail or wall-mount, 35 mm wide, mounting height 55 mm 

  Universal supply AC/DC 24-240 V 

 

The sensor changes its resistance with the temperature (app. 0,385 Ohm/°C). The measuring transducer 
measures the resistance with a current <1 mA and transduces it into a signal DC 0-10 V or 0/2-20 mA that is 
proportional to the temperature. At break of sensor or wire the output signal is app. 22 mA / 12 V, at short 
circuit 0 mA / 0 V. 

 

The output can be connected to displays, PLCs or monitored for over- or under-temperature.

 

 

Connecting diagram 

See 1 Display and controls 
 

Important Information 

 

 

DANGER! 
Hazardous voltage! 
Will cause death or serious injury. Turn off and lock out all power 
supplying this device before working on this device. 

 
 

 

Attention! 
The device has a universal power supply, that is suitable for DC- and AC voltages. 
Before connecting the device to supply- voltage make sure that the 
connected voltage corresponds with the voltage on the lateral type on the device. 

 
 

Observe the maximum temperature permissible when installing in switching cabinet. Make sure 
sufficient space to other equipment or heat sources. If the cooling becomes more difficult e.g. 
through close proximity of apparatus with elevated surface temperature or hindrance of the 
cooling air, the tolerable environmental temperature is diminishing. 

 

To use the equipment flawless and safe, transport and store properly, install and start professionally and 
operate as directed. 
Only let persons work with the equipment who are familiar with installation, start and use and who have 
appropriate qualification corresponding to their function. They must observe the contents of the instructions 
manual, the information which are written on the equipment and the relevant security instructions for the 
setting up and the use of electrical units. 
The equipment is built according to  DIN / EN and checked and leave the plant according to security in 
perfect condition. If, in any case the information in the instructions manual is not sufficient, please contact 
our company or the responsible representative. 
To  maintain  this  condition,  you  must  observe  the  safety  instructions  in  this  instruction  manual  titled 
“Important  Information”.  Failure  to  follow  the  safety  instructions  may  result  in  death,  personal  injury,  or 
property damage to the equipment itself and other equipment and facilities. 
Instead of the industrial norms and regulations written in this instruction manual valid for Europe, you must 
observe out of their geographical scope the valid and relevant regulations of the corresponding country. 

Summary of Contents for TMU100V

Page 1: ...ehl de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual TMU100V updated 2018 11 12 sm TMU100V 12100 0702 01 Page 1 6 www ziehl de Measuring Transducer for Potentiometers ...

Page 2: ...nd short description Model TMU100 Pt100 measuring transducers are suitable for measuring temperatures with sensors Pt100 RTD Zero and Full scale can be freely set within the whole range 199 850 C To do this only resistors with the according value or a Pt 100 decade is connected The adjustment is done by pressing a button The built in universal power supply AC DC 24 240 V allows the connection to a...

Page 3: ...temperature permissible when installing in switching cabinet Make sure sufficient space to other equipment or heat sources If the cooling becomes more difficult e g through close proximity of apparatus with elevated surface temperature or hindrance of the cooling air the tolerable environmental temperature is diminishing To use the equipment flawless and safe transport and store properly install a...

Page 4: ...ro Wait until LED power starts blinking and release button Leave commissioning mode by pressing buttons Zero and Full scale simultaneously Commissioning mode is finished automatically after 10 min Set values remain stored also when power is switched off 7 2 Adjusting of Zero Simulate temperature for zero at input of TMU100V with a resistor or a decade for Pt 100 Resistance see table in this manual...

Page 5: ... Fault burden 250 Ω burden 250 Ω 0 3 of the current For parameter error Full scale approx 22mA 12V are output For parameter error zero approx 0mA 0V are output Test conditions EN 61010 1 Rated impulse voltage 4000 V Overvoltage category II reinforced insulation Pollution degree 2 Rated insulation voltage Ui 250 V On period 100 EMC tests Emission EN 61000 6 3 Immunity EN 61000 6 2 Installation cond...

Page 6: ...t part of delivery Weight approx 130 g Subject to technical modifications 10 Housing Type V2 Dimension in mm 1 Oberteil cover 2 Unterteil base 3 Riegel bar for snap mounting 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung Ø 4 2 mm for fixing to wall with screws Ø 4 2 48 58 45 3 61...

Reviews: