background image

(datum / name): 10.12.08 Su/Fz 

Z. Nr.: 1004 0710.2 

Page  2  von  4 

Type: MSF 220 SE 

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected] 

Technical Data 

 

 

 

Supply Voltage US 

see type plate on the device 

 Us: 

DC/AC 24 - 240 V

 

  Tolerance 

DC 20,4 – 297 V,  AC 20 – 264 V 

  Frequency 

0, 40...500 Hz, at AC 80 V: 10...500 Hz 

  
Us: 

DC/AC 90 – 240 V

  

  Tolerance 

DC 80 – 297 V, AC 80 – 264 V 

  Frequency 

0, 40...500 Hz, AC 10...500 Hz 

 
Power consumption 

<2 VA 

 

PTC-resistor connection

 

2 x 1...6 PTC in series 

Cut-out point 

2,8...3,6 k

, typ. 3,2 k

 

Reclosing point 

1,8...2,4 k

, typ. 2,1 k

 

Collective resistance of cold sensors 

 1,5 k

 

Terminal voltage (sensors) 

 2,5 V at 

 250 

 

 

 

 7,5 V at 

 4 k

  max. 5 mA 

 

Relay output

 

contacts AgNi 015 

Switching voltage 

max. 400 V 

 

Switching current 

max. 8 A 

 

Switching power 

max. 2000 VA 

 

Rated continious current Ith 

5 A 

 

Rated operational current Ie 

2 A AC15  400 V 

2A DC13 24 V    3 A AC15  250 V 

Prefuse for device and contacts 

AC: T 4  A 

DC: T 2 A 

Mechanical contact life 

3 x 10

7

 operations 

Electrical contact life  

1 x 10

5

 operations (at max. switching capacity) 

Factor of reduction at cos = 0.4 

0.5 x max. switching capacity 

Switching-on delay 

app. 2 s 

 

Testing conditions

 

EN 60947, EN 50178 

Rated insulation voltage 

AC 250 V 

Isolation 

EN 60664 

Rated impulse voltage 

400 V 

Contamination level 

Transformer 

EN 61558 

On period 

100 % 

max. ambient temperature 

-20 ... +55 °C, EN 60068-2-2 dry heat 

 

Housing:

 

design S-12, plug-in housing 

Dimensions (H x W x D) 

82 x 42 x 121 mm 

Line connection 

12-pole, max. 2 x 1.5 mm

2

 each 

Protection Housing 

IP 40 

Protection contacts 

IP 20 

Panel inclination 

any 

Mounting 

snapable on 35 mm standard rail according to  

 

 

EN 60715 or assembly with scrwes M 4 

Weight   

app. 250 g 

 
Subject to technical modifications

 

Summary of Contents for MSF 220 SE

Page 1: ... not available and the secondary voltage of the monitored transformer is being used The MSF 200 SE can furthermore be used advantageously when combining it with operating current releases For additional devices the control voltage is available at terminal 1 time delayed In case of a breakdown of the supply voltage the control voltage is available at terminal 7 and can be used as a message Attentio...

Page 2: ...current max 8 A Switching power max 2000 VA Rated continious current Ith 5 A Rated operational current Ie 2 A AC15 400 V 2A DC13 24 V 3 A AC15 250 V Prefuse for device and contacts AC T 4 A DC T 2 A Mechanical contact life 3 x 107 operations Electrical contact life 1 x 105 operations at max switching capacity Factor of reduction at cos 0 4 0 5 x max switching capacity Switching on delay app 2 s Te...

Page 3: ...rminals A1 and A2 When device is ready for operation relays K1 and K2 switch on immediately the LED s are off After approx 2 s relay K3 picks up terminals 31 14 31 24 31 34 are connected Relay K1 releases as soon as the input at terminal T11 T12 becomes high resistive Relay K2 releases as soon as the input at terminal T21 T22 becomes high resistive Relay K1 K2 pick up as soon as the inputs at term...

Page 4: ... 12 K1 34 32 K3 2 circuit 2 K2 6 3 circuit 1 PTC s alarm 1 alarm 2 operation 2 delayed input signal of terminal 3 alarm 3 A2 A1 Us DC AC T11 T21 T12 T22 input signal operation 1 104 5 82 36 23 5 5 41 5 80 34 1 2 3 4 5 6 7 8 9 10 11 12 82 41 5 17 7 5 5 11 5 17 5 5 10 1 2 3 1 1 2 6 Jackets for co ding pins 14 27 5 2 3 1 Cable bushing Mounting bore hole Unlatching only with rail mounting Base 41 16 3...