Important notes 

 

 

 

 

DANGER!

   

 

 

 

Hazardous voltage! 

 

 

 

Will cause death or serious injury. Turn off and lock out 

 

 

 

all power supplying this device before working on this device! 

 

To use the equipment flawless and safe, transport and store properly, install and start professionally and 
operate as directed. 
Only let  persons work with the equipment who are familiar  with installation,  start and use and who have 
appropriate qualification corresponding to their function. They must observe the contents of the instructions 
manual, the information which are written on the equipment and the relevant security instructions for the 
setting up and the use of electrical units. 
 
The equipments are built according to EN60947 and checked and leave the plant according to security in 
perfect  condition.  To  keep  this  condition,  observe  the  security  ins

tructions  with  the  headline  „Attention“ 

written in the instructions manual. Ignoring of the security instructions may lead to death, physical injury or 
damage of the equipment itself and of other apparatus and equipment. 

If, in any case the information in the instructions manual is not sufficient, please contact our company or the responsible representative. 

Instead of the industrial norms and regulations written in this instructions manual valid for Europe, you must 
observe out of their geographical scope the valid and relevant regulations of the corresponding country. 

 
 
 

Installation 

 

 

 

Attention! 

 

 

 

Observe safety rules and standards. Notice safety remarks! 

 

 

  The device can be mounted on 35 mm rail according EN 60715 or with screws M4 (Option) 

  The devices must be installed in an enclosure of international protection class IP 5x or better. 

  Housing overall width 35 mm (2 TE) 

  Terminals with screw mounting M3 maximum tightening torque 0,8 Nm 

 

When installing the device into the switchgear cabinet, please observe the max. admissible 
temperature. Care for both, sufficient clearance to other devices or sources of heat or 
enough forced draught. If cooling is made more difficult, e.g. close devices with increased 
surface temperature or by handicap of airflow cooling, the permissible ambient temperature 
has to be reduced. 

The lines of the sensor circuit are to be routed as separate control lines. The use of lines of 
the supply cable or other mainstream lines is not permissible. If extreme inductive or 
capacitive stray effects are to be expected by parallel cables of the power installation, 
shielded control lines should be used. 

 

 

  

Attention! TMP tripping relays with supply voltage DC/AC 24 V without  

 

  

potential separation are intended to use at power supplies according SELV  

 

  

or PELVwhere protected wiring is used. 

 

 

 

!

Summary of Contents for MS220C

Page 1: ...s und MINIKA Strom und Spannungsrelais Messgeräte MINIPAN Schaltrelais und Steuerungen Messumformer Netz und Anlagenschutz Operating Instructions MS220C updated 2017 11 08 Su MS220C 12150 0703 03 Page 1 8 www ziehl de PTC thermistor relay TMP tripping device Power supply AC and AC DC E179399 Approvals marking see type plate on the device ...

Page 2: ...atures arise related to TNF detector operating temperature Tripping temperature Reset temperature 1 PTC thermistor TNF 15 K TNF 5 K 3 PTC thermistors in series TNF 5 K TNF 5 K 6 PTC thermistors in series TNF TNF 20 K 3 Application and short description ZIEHL PTC resistor relays protect motors transformers machines and equipment against thermal overload With ZIEHL PTC Sensors MINIKA applied they of...

Page 3: ...the sensors In cold state the resistance is 250 Ω per sensor sensor circuit 1 5 kΩ The relay has picked up and contact 11 14 is closed The resistance of the sensor rises rapidly at nominal response temperature NRT The relay release at a resistance between 2650 Ω R 4000 Ω The relay switches on automatically at a resistance 1650 Ω R 2650 Ω 5 Connecting diagram Us supply voltage S1 push button OFF S2...

Page 4: ...the industrial norms and regulations written in this instructions manual valid for Europe you must observe out of their geographical scope the valid and relevant regulations of the corresponding country 8 Installation Attention Observe safety rules and standards Notice safety remarks The device can be mounted on 35 mm rail according EN 60715 or with screws M4 Option The devices must be installed i...

Page 5: ... with a suitable measuring instrument With a resistance 50 Ω the sensor circuit is to be examined for short circuit Attention Check PTC s only with measuring voltages of 2 5 V 10 Trouble shooting Relay does not pick up Please check The supply voltage Us at terminals A1 A2 The PTC sensors at terminals T1 T2 The resistance of a PTC set must be within 0 Ω R 1500 Ω The terminal voltage T1 T2 is to be ...

Page 6: ...perature monitor cut out point 4 kΩ Temperature monitor reclosing point 1 65 kΩ Relay output 11 12 14 EN 60947 5 1 Contacts 1 change over contact co Rated operational voltage Ue 250 V Switching voltage max AC 415 V Switching current max 6 A Conventional free air thermal current Ith 5 A Making current 20 ms 30 A Min operational current at 12 V 10 mA Switching power AC 1 max 1250 VA Switching power ...

Page 7: ...class UL 94 V 2 Protection class housing terminals EN 60529 IP 40 IP20 Mounting EN 60715 35 mm standard rail according or with screws M4 Weight app 120 g with transformer app 80 g others Screw Terminals M 3 5 Tightening torque 0 8 Nm 7 lb in Line connection solid wire 2 x 0 5 2 5 mm2 AWG 20 14 Stranded wire with insulated ferrules 2 x 0 34 1 5 mm2 AWG 20 16 Insulation strip length min 8 mm Subject...

Page 8: ...MS220C 12150 0703 03 Seite 8 8 www ziehl de 13 Form C Dimension in mm ...