Type: Minipan 300
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected]
Examples:
InPU
ScAL
InLo
InHi
diLo
diHi
dP
Input 0..10 V
Display 30..100 %
10
USEr
0.00
10.00
30
100
0000.
Input 4..20 mA
Display 0..100 %
4-20
USEr
4.00
20.00
0
100
0000.
Input 0..20 mA
Display 50.0..500.0
0-20
USEr
0.00
20.00
500
5000
000.0
Input 10..90 V
Display 50.0..500.0
100
USEr
10.0
90.0
500
5000
000.0
Input 0-60 mV
Display 0,0..30.0
300
USEr
0
60
0
300
000.0
Input 2..5 V
Display -50.0..100.0
10
USEr
2.00
5.00
-500
1000
000.0
Confirm and change to next menu with Set.
Delay of Display (recommended at unstable signals)
Select menu item with Up/Down until display
ddiS
and programmed value alternate.
Change into parametrizing mode with Set and set delay of display with Up/Down.
Now the measured value will be written into the display every 0,1 ... 2 s.
Confirm and change to next menu with Set.
Fixed Digits (recommended when measured signal is very unstable or changing rapidly)
Select menu item with Up/Down until
F
and the fixed digits blinking are displayed. When no
fixed digit is programmed, the last 2 digits are dark.
Set the fixed digits:
Fi
no
Fi 0
last digit fixed (
0
)
Fi00
last digit fixed (
00
)
These digits display 0, independent from measured value.
Confirm and change to next menu with Set.
Code-lock
Select menu item with Up/Down until display
Code
programmed state alternate.
Here the parameters can be protected by activating the code-lock. After pushing Set,
Pin
is
displayed. Change to
Pin 504
with buttons Up/Down (factory setting). After pushing Set the
code-lock can be activated or de-activated. After pushing Set again, an individual
Pin
Can be selected (write down)
With activated code-lock, all parameters can be seen but not changed any more.
In case of problems with the code-lock (forgotten
Pin
), the lock can be switched off and the
Pin
can be set back to
504
,by pushing the button Set/Reset while connecting the device to
supply voltage until
Code
/
ofF
is displayed.