U-EK230E
L-BAL-E185-GB 2023/10 Index 005
11660-0711-03
6/12
Power / Load
≤ 2 mW
Line capacity max.
0.2 µF
Temperature monitor cut-out-point
3.3 kΩ …3.65 kΩ …3.85 kΩ
Temperature monitor reclosing point
1.7 kΩ …1.8 kΩ …1.95 kΩ
Short circuit monitor cut-out-point
≤ 20 Ω
Short circuit monitor reclosing point
≤ 40 Ω
Reset input (Y1, Y2)
Potential free contact (no)
Current
1 mA
Voltage
< 30 VDC
Relay output (11, 12, 14)
EN 60947-5-1
Contacts
1 change-over contact (co)
Switching voltage
max. AC 400 V
Switch-on current (NO)
AC 15 A 4s 10% ED
min. voltage / current
12 V 10 mA
Conventional thermal current Ith
max. 5 A
Switching power max. AC cos φ = 1
2000 VA
Switching power max. DC (ohm)
0.25 A 300 V; 0.35 A 150 V; 1 A 60 V; 8 A 30 V
Contact life electrical cos φ = 1
2 x 10
5
operating cycles at 250 V / 2 A
1 x 10
5
operating cycles at 250 V / 5 A
Contact life mechanical
3 x 10
7
operating cycles
Recommended fuse (NO)
4 A time-lag or miniature circuit-breaker MCB B4
Recommended fuse (NC)
3.15 A time-lag
Utilization category
Rated operational current
Rated operational voltage
AC-15 Ie = 3 A Ue = 250 V
DC-13 Ie = 2 A Ue = 24 V
DC-13 Ie = 0.4 A Ue = 120 V
DC-13 Ie = 0.2 A Ue = 250 V
UL electrical ratings
250 VAC, 3 A, general use
C300
Test conditions
IEC/EN 60947-8
Rated impulse voltage
4000 V
Overvoltage category
III
Pollution degree
2
Rated insulation voltage Ui
320 V
Transformer
EN 61558-2-6 (VDE 0570)
Proof Test Voltage
2500 VAC 50 Hz
EMC - Immunity
EN 61000-6-2
EMC - Emission
N.a., f
mainosc
< 9 kHz
On-period
100 %
Ambient conditions
Fitting position
any
Rated ambient temperature
-20 °C ... +55 °C
Rated storage Temperature
-2
0 °C …+70 °C (1K21 EN 60721-3-1)
Altitude
≤ 2000 m above sea level.
Climatic conditions
5-85 % rel. F., no condensation (
3K22 EN60721-3-3
)
Vibration DIN EN 60068-2-6
2…25 Hz ±1.6 mm 25 ... 150 Hz 5 g
Vibration DIN EN 60947-8
2 … 13.2 Hz ± 1 mm 13.2 ... 100 Hz ± 0.7 g
Shock DIN EN 60947-8
half sine, 10 g, 11 ms
Housing
Design V2
Dimensions (W x H x D) mm
35 x 90 x 58 mm
Width
2 M
Plastic material
PA66
Fire protection class
UL 94 V-2
Protection class housing EN 60529
IP30
Mounting EN 60715
Snap mounting on 35 mm standard rail EN60715
Optional: Screw mounting
M4 screws (additional bar not included)
Weight
approx. 117 g
Terminal connection
Screw mounting M3
Protection class terminals EN 60529
IP20
Tightening torque
0.5 Nm