Operating Instructions PAE10E-M / PSE-6/14V
Date 0618
R-TBL95_35_GB 0618 Part-No. 00158612-GB
- 6 -
4. Installation
4.1 Mounting
•
Assemble the device on a clean and stable base. Do not distort during assembly! Use the appropriate mounting
devices for proper installation of the unit!
•
Do not mount equipment on vibrating base!
•
Use the appropriate fixing equipment. The plastic washers must be installed between the screw heads and the
housing for models with mounting holes on the inside of the housing!
•
Install the device away from transport routes. However, ensure however that the device is still easily accessible!
•
Depending on the housing model cut off necessary cable inlets respectively to the cable diameter. Or alternative use
cable inlet for cable glands. Metal sheet housings are supplied with stoppers. Any cable ducts openings not used
must be sealed!
•
Protect the device from direct exposure to sunlight!
•
The device is designed for vertical installation (cable inlet down). A horizontal or reclined installation is only
permissible after consultation with the manufacturer.
•
Be sure to observe proper heat dissipation (
)
Technical data, “heat dissipation”)
4.2 Minimum space requirement
In order to ensure sufficient ventilation of the device, clearance on all sides of at
least 50 mm has to be maintained to the housing walls, switch cabinet doors,
wiring ducts, etc. The same clearance applies to the installation of several
devices next to each other (
)
illustration).
When installing several devices on top of each other, the danger of reciprocal
heating exists. This layout is only then permissible when the air suctioned from
the upper unit does not become warmer than the permissible ambient
temperature (
)
Technical data). I.e., a correspondingly larger clearance or
thermal shielding is required.
4.3 Outdoor installation (PSE-6/14V or PAE10E-M in empty case IP 54)
Outdoor installation in IP 54 is possible up to -20° C, if device is not switched off.
4.4 Temperature influences during commissioning
To prevent functional faults, no condensing humidity must be allowed to enter the controller. The controller should
therefore be stored at room temperature!
4.5 Systems with current-operated circuit-breaker
Owing to possible leakage currents occurring when the device is switched on, it is advisable to use time-delay current-
operated circuit-breakers. This prevents false triggering.
4.6 Potential of control voltage connections
As a result of the ex factory connection between a "GND" terminal and the "PE" connection, the control voltage
connections are, for safety reasons, applied to the protective-conductor potential. If, in exceptional cases, disconnection
of the potential is necessary, this connection can be removed.
{
If this connection is removed, it must be ensured that the maximum external voltage at the control
voltage connections does not exceed
20 V
(between the "GND" terminals and the "PE" protective
conductor).
{
An insulated power cable must be used for the sensor cable.
min. 50 mm