
5.6
Motor protection
Motor protection is possible by connecting thermostats
“
TB
”
(thermal contacts) or thermistors
“
TP
”
(PTC).
The jumper on the device circuit board must be plugged according to the used thermal protector (see
fi
gure
terminal compartment).
Motor with thermistors
“
TP
”
For motor with thermistors
“
TP
”
jumper plugged at bottom (factory setting).
A maximum of six single thermistors (DIN 44081 or DIN 44082) is permissible which are con-
nected in series.
TP
Motor with thermostats
“
TB
”
For motor with thermostats
“
TB
”
the jumper must be plugged at the top.
TB
When a connected thermostat or thermistor responds (interruption between the two terminals
“
TB/TP
”
) the device switches off and does not switch back on.
Relais
“
K1
”
is de-energized, terminals
“
13
”
-
“
14
”
interrupted. The signal lamp
fl
ashes in code
|
15
|
(see Diagnostics / Faults).
"
Switch back on after the drive has cooled down, i.e. in case of a connection between the terminals
“
TB/TP
”
, by switching the line voltage off and back on.
5.7
Analog input
“
E1
”
for setting fan speed
The device has an analog input for setting the fan speed. Connection
“
E1
”
/
“
GND
”
(Analog In 1).
The internal jumper
“
E1.1
”
is factory set in the position for a 0...10 V or PWM speed setting signal.
For a 0...20 mA signal the plug
“
E1.1
”
must be replugged.
Danger due to electric current
•
Do not replug the jumper under voltage, observe the safety instructions!
•
Make sure the signal has the correct polarity!
•
Never apply line voltage to analog inputs!
Possibilities for speed setting
0...10 V (factory setting)
Control via external setting signal 0...10 V
or
Speed setting by external potenziometer (10 k
Ω
) at terminals
“
+10 V
”
and
“
GND
”
pick of-off at terminal
“
E1
”
.
E1
D1 GND
0...10 V
+
An
a
lo
g
I
n
1
E1.1
V
E1
D1 GND 10V
An
a
lo
g
I
n
1
1
0
V
D
C
O
u
t
10 kΩ
13.06.2014
i_jumper_motor_mounted_0_10v.eps
Operating Instructions
PMIcontrol Basic-M
–
model series FSDM5...46
Electrical installation
L-BAL-E300-GB 1905 Index 001
Part.-No.
31/48