5.11
Open-Collector output
“
A1
”
(status / tacho)
Open-Collector pulse output for status display or speed display.
Status display
(function for factory setting)
Depending on the operating state of the device, the output
“
A1
”
is switched to
GND potential for a certain number of pulses.
The status of the device can be displayed by this digitally coded signal.
With the output voltage
“
+10 V
”
a standard LED / low-power LED can be
controlled by using a pull-up resistor.
This lights when the output
“
A1 Status Out OC
”
(OC = Open-Collector) is on GND
potential.
The details of which pull-up resistor needs to be used depend on the speci
fi
cation
on the LED that is used.
Explanation of
fl
ash codes
Diagnostic / Status Out with
fl
ash code.
Pull Up
10V
A1
GND
06.11.2013
i_ecblue_a1_status_oc.eps
200...300 Ω
Tacho out
Alternatively, via output
“
A1
”
, the current motor speed can be output.
The frequency (duty cycle 50 : 50) that can be measured by a pull-up resistor at
the output
“
A1
”
corresponds to the motor speed.
Example: 10 Hz x 60 = 600 rpm
Pull Up
10 V
A 1
GND
Hz
n = f x 60
5 kΩ
06.11.2013
i_ecblue_a1_tacho_oc.eps
200...300 Ω
A1
more speci
fi
cations
Technical data!
5.12
Open-Collector output
“
A2
”
(operation)
Via the output
“
A2 Operation Out OC
”
an operating indication is possible.
With the output voltage
“
+10 V
”
a standard LED / low-power LED can be
controlled by using a pull-up resistor.
This lights when the output
“
A2 Operation Out OC
”
(OC = Open-Collector) is on
GND potential.
By fault the output
“
A2
”
is switched to GND potential.
The details of which pull-up resistor needs to be used depend on the speci
fi
cation
on the LED that is used.
Pull Up
10 V
A 2
GND
06.11.2013
i_ecblue_a2_operation_oc.
200...300 Ω
5.13
Potential at control voltage connections
The connections for the control voltage (< 30 V) relate to the common GND potential (exception: relay
contacts are potential-free). There is a potential isolation between the connections for the control
voltage and the PE conductor. It must be ensured that the maximum external voltage at the con-
nections for the control voltage cannot exceed 30 V (between the
“
GND
”
and
“
PE
”
conductor
terminals). A connection to the PE conductor potential can be made if required;
fi
t a bridge between
the
“
GND
”
terminal and the
“
PE
”
connection (terminal for shield).
Assembly instructions
ECblue
Electrical installation
L-BAL-F056-GB 1939 Index 003
Part.-No. 00700562-GB
23/35