5.3
Accessories: connection box
A connection box is available as an accessory for the standard connecting cables, which enables the
simple, quick and safe wiring of multiple fans.
Connection box RJ45, Part-No. 380085
Attention: only this version is compatible with the RJ45 connection of the control cable!
Front view
Back
26.07.2013
v_ecblue_terminalbox_380085.vsd
3
4
5
6
7
8
BUS2
BUS1
Service
RJ45
2
1
1
Connection control fan (RJ45). The LEDs of the connection box are supplied from the connected fan (output v10 V).
2
Connection line fan (tension clamp connection 0.5 - 1.5 mm
2
fl
exible with wire end ferrule)
3
Line input connection box (Wieland plug series GST 18i3, suitable socket part e.g. GST 18i3 S B1 Z R1 or GST 18i3 1 F B2
Z R1)
4
LED green = Operation / Error
fl
ash code
5
LED red = fault
6
BUS1 (RJ45)
7
Service (RJ45)
8
BUS2 (RJ45)
5.4
EMC-compatible installation of control lines
Pay attention to suf
fi
cient distance from powerlines and motor wires to prevent interferences. The
control cable may not be longer than 30 m. Screened control cables must be used when the cable
length is longer than 20 m. When using a shielded cable connect the shielding to one side only, i.e.
only to the signal source with the protective earth (keep cable short and with as little inductance as
possible!).
5.5
Voltage supply
5.5.1
Line voltage
Danger due to electric current
•
It must be strictly observed that the line voltage complies with speci
fi
ed on the rating plate and lies
within the allowable tolerance speci
fi
cations (see technical data).
•
Between the voltage supply of the device and the protective earth
“
PE
”
is in no case a higher voltage
permissible than the indicated line voltage of the device!
•
Mains connection to: PE, L1 and N.
•
Attention!
–
To activate the on current limitation, you must wait at least 90 seconds after switching off the line
voltage before switching back on!
5.5.2
Required quality attributes for the mains voltage
Danger due to electric current
The mains voltage must comply with the EN 50160 quality characteristics and the de
fi
ned standard
voltages in IEC 60038!
Assembly instructions
ECblue
Electrical installation
L-BAL-F056-GB 1939 Index 003
Part.-No. 00700562-GB
16/35