9.2
Temperature control
2.01
and
2.02
2.01
Temperature control with one sensor
2.02
Temperature control with 2 sensors.
Automatic control to the temperature sensor with higher value.
9.2.1
Setting for operation as Temperature controller
%
set
0
100
18.07.2011
v_set_pxet.VSD
Setpoint
For
Temperature control with passive sensors type TF.. (KTY), PT1000
Setting range: 0 - 100 % -26...75
°
C (measuring range of controller: -50...+150
°
C)
For
control with active sensors (0 - 10 V, 4 - 20 mA)
Setting range: 0 - 100 %
measuring range of sensor
Scale 0 - 100 % -25...75
°
C for Temperature control with passive sensors
set
[%]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95 100
[
°
C]
-25
-20
-15
-10
-5
-0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
19.07.2011
v_pband_pxet.VSD
%
Pband
5
30
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
For
Temperature control with passive sensors type TF.. (KTY), PT1000
Setting range: 5 - 30 %
5 - 30 K
For
control with active sensors (0 - 10 V, 4 - 20 mA)
Setting range: 5 - 30 %
5 - 30 % measuring range of sensor
18.07.2011
v_nmin_pxet.VSD
%
n-min
0
100
Minimum output voltage (basic speed)
Setting range: 0 -
“
n-max
”
18.07.2011
v_nmax_pxet.VSD
%
n-max
0
100
Maximal output voltage (speed limiter)
Setting range: 100 % - 0 (takes priority over
“
n-min
”
)
Output voltage depending on load
“
Adjusting of CosPhi for motor
”
.
Operating Instructions
Dcontrol
–
model series PKDM6..80
Setting for operation
L-BAL-E143-GB 1914 Index 009
Part.-No.
26/40