8
Start-up
8.1
Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the hazardous area.
9
Setting for operation
9.1
Speed controller
1.00
and
1.01
9.1.1
Setting for operation as Speed controller
1.00
Ansteuerung
ü
ber internes Potenziometer
1.01
Setting via external signal or external potentiometer
(factory setting)
%
set
0
100
18.07.2011
v_set_pxet.VSD
1.00
Potenziometer
“
set
”
(DIP 2 =
|
ON
|
)
Setting range: Output voltage from approx. 0 - 100 % of connected line voltage or in
range of settings
“
n-min
”
up to
“
n-max
”
.
Signal to:
E1
E1
GND
14.02.2008
v_signal_e1.vsd
1.01
signal
“
E1
”
(factory setting: DIP 2 =
|
OFF
|
)
•
Control via external setting signal
0...10 V
•
By external wiring with a resistor (499
Ω
/ 0,25 W) between the terminals
“
E1
”
and
“
GND
”
parallel to the input signal, activation with a
0...20 mA
signal is
possible.
Setting range: Output voltage from approx. 0 - 100 % of connected line voltage or in
range of settings
“
n-min
”
up to
“
n-max
”
.
(Potentiometer
set
without function)
18.07.2011
v_nmin_pxet.VSD
%
n-min
0
100
Minimum output voltage (basic speed)
Setting range: 0 -
“
n-max
”
18.07.2011
v_nmax_pxet.VSD
%
n-max
0
100
Maximal output voltage (speed limiter)
Setting range: 100 % - 0 (takes priority over
“
n-min
”
)
Output voltage depending on load
“
Adjusting of CosPhi for motor
”
.
Operating Instructions
Dcontrol
–
model series PKDM6..80
Start-up
L-BAL-E143-GB 1914 Index 009
Part.-No.
24/40