5.8
Output voltage 0 - 10 V (A1 = Analog Out 1)
Connection to terminals
“
A1
”
-
“
GND
”
=
“
Analog Out 1
”
(I
max
10 mA).
It is not permissible to connect outputs of several devices to each other!
The function of the signal output A1 (Analog Out 1) can be determined by
DIP 8
(
basic settings / dipswitches).
DIP 8 =
|
OFF
|
Constant v 10 V for external potentiometer (factory setting)
DIP 8 =
|
ON
|
0 - 10 V
modulation 0 - 100 %
•
Proportional the internal control of modulation with consideration
“
n-min
”
and minimum air
switch-off. The setting for
“
n-max
”
is not considered.
•
For enable
“
OFF
”
it goes
not back to
“
0 V
”
.
•
For motor fault the output signal remains for a slave controller (
“
Master-Slave
”
combina-
tion).
5.9
Voltage supply for external devices (+24V, GND)
A voltage supply is integrated for external devices e.g. a sensor (max. current load see technical
data).
In case of overload or short circuit (24 V
–
GND), the external power supply is shut down (multi-fuse).
The device performs a
“
Reset
”
and continues operation.
•
It is not permissible to connect voltage outputs of several devices to each other!
•
It is not permissible to connect voltage outputs in the device to each other!
5.10
Digital inputs (D1, D2)
Activation via
fl
oating contacts, a low voltage of approx. 24 V DC is connected.
Attention!
No disconnection (isolation) when turned off, in accordance with VBG4
§
6)!
Never apply line voltage to the digital input!
It is not permissible to connect inputs of several devices to each other!
5.10.1
D1 = Enable (Device ON / OFF)
Electronic disconnection and Reset after motor fault via
fl
oating contact at terminals
“
D1
”
-
“
D1
”
•
Device
“
ON
”
for closed contact.
•
Controller
“
OFF
”
with opened contact.
•
Relais
“
K1
”
remains energized, terminals 11 - 14 bridged. The signal lamp
fl
ashes in code
|
1
|
(
Diagnostics / faults).
5.10.2
D2 = Reverse action of the control function
For operation as P-Controller
2.01
..
3.02
, the digital input
“
D2
”
can used for reverse of control
function.
For the effect of the regulation there are two functions:
•
“
Val > Set = n+
”
increasing modulation for increasing actual value over setpoint.
•
“
Val < Set = n+
”
increasing modulation for decreasing actual value below setpoint.
When terminals
“
D2
”
-
“
D2
”
bridged, the device works with the opposite function than the one set with
DIP 4!
Operating Instructions
Dcontrol
–
model series PKDM6..80
Electrical installation
L-BAL-E143-GB 1914 Index 009
Part.-No.
16/40