4 Mounting the module
Danger due to electric current
•
Always read the safety instructions chapter before mounting!
•
The terminating device (fan, converter) in which the module is to be installed
must be disconnected from the line voltage for at least 3 minutes before opening!
Attention, electrostatic sensitive devices!
•
Damage to electronic components by electrostatic charging must be prevented!
•
Touch the protective earth connection in the terminal to equalize the potential
immediately before removing the module from the packing. This applies
regardless of whether the device is already connected to the line.
•
Equalize the potential again shortly before installation if the module is not
installed immediately after unpacking.
•
After unpacking the module, check for possible transport damage and insert it in
the slot provided. Do not touch the connection!
•
ECblue: Mount the module in the housing with the two enclosed screws
(permissible tightening torque M
A
= 1.3 Nm).
•
Fcontrol Basic, Icontrol Basic, PMcontrol: Press the module into the retaining
clips.
•
Permissible tightening torque of connection terminals M
A
= 0.24 Nm.
Example for mounting the add-on module
Operating Instructions
AM-LON
Mounting the module
L-BAL-E166-GB 1610 Index 002
Part.-No. 00163375-GB
5/9