11.1.1
Performance reduction during elevated ambient temperatures
The maximum permissible temperature for the rated current at rated voltage is speci
fi
ed as rated
temperature.
Since the dissipation of the power loss (heat development) in the device is decisively dependent on
the ambient temperature, the max. load must be reduced at an ambient temperature above the rated
temperature (see following table)!
The average value measured during a 24 h period must be 5 K under the max. ambient temperature.
For installation in a switch cabinet, the device
’
s dissipation and its possible affect on the ambient
temperature must be taken into consideration!
Maximal motor current depending on ambient temperature
Type
Part-No.
40
°
C
45
°
C
50
°
C
55
°
C
[A]
[A]
[A]
[A]
PXET6Q
303612
6.0
6.0
5.5
5.0
PXET10Q
303613
10.0
9.5
9.0
8.0
Operating Instructions
Acontrol
–
model series PXET6Q / PXET10Q
Enclosure
L-BAL-E016-GB 1925 Index 007
Part.-No.
28/32