6.2
Internal Setting
Attention!
The controller housing cover may only be removed when the power line has been switched off!
It is generally forbidden to carry out work on electrical live parts. Protection class of the device when
open is IP 00! It is possible to touch hazardous voltages directly.
18.07.2011
v_pxet_q_intern_bed.VSD
%
n-max
0
100
%
set
0
100
%
n-min
0
100
V
°C
mA
E1
ON
OFF
10
9
8
7
6
5
4
3
2
1
DIP S1
%
Pband
5
30
Potentiometer
set
For main switch position
“
Auto
”
function depending on internal switch DIP 2 and selected mode (for
main switch position
“
Hand
”
without function).
•
For
Speed controller
1.01
and DIP 2 =
|
OFF
|
(factory setting) without function
•
For
Speed controller
1.01
and DIP 2 =
|
ON
|
setting of output voltage 0 - 100 %
At
P controller
2.01 3.01
and
PI controller
4.01
can be selected with DIP 2 whether the setpoint
adjustment is made via this internal potentiometer or via the external potentiometer (the internal
potentiometer is active at the factory (DIP 2 =
|
OFF
|
).
•
For
temperature control
2.01
with passive sensors TF.. (KTY).
setting range: 0 - 100 %
-26...76
°
C (measuring range of controller).
•
For
control with active sensors
3.01
,
4.01
(0 - 10 V, 4 - 20 mA).
Setting range: 0 - 100 %
measuring range of sensor.
Potentiometer
Pband
Function dependently on selected mode of operation
•
For
Speed controller
1.01
: without function
•
P-controller
2.01
,
3.01
–
For
temperature control with passive sensors TF.. (KTY).
Setting range: 5 - 30 %
5.1 - 30.6 K.
–
For
control with active sensors (0 - 10 V, 4 - 20 mA).
Setting range: 5 - 30 %
5 - 30 % measuring range of sensor.
•
PI-Controllerr
4.01
–
For
control with active sensors (0 - 10 V, 4 - 20 mA).
Setting range: 5 - 30 %
5 - 100 % measuring range of sensor.
Potentiometer
n-min
Minimal output voltage (basic speed)
Setting range: 0 - 100 % (
“
n-min
”
takes priority if over
“
n-max
”
)
Potentiometer
n-max
Maximal output voltage (speed limiter)
Setting range: 100 % -
“
n-min
”
Jumper
E1
Basic setting for kind of signal at analog input
“
E1 = Analog In 1
”
Dipswitch
S1
Basic setting for device function
Operating Instructions
Acontrol
–
model series PXET6Q / PXET10Q
Operating and display elements
L-BAL-E016-GB 1925 Index 007
Part.-No.