10.1
If controller doesn
´
t work correctly
Information
Setting of dip switches in principle only when device is not under voltage.
If the device is on mains supply modi
fi
cations will partly not be identi
fi
ed and realized.
Attention!
It is generally forbidden to carry out work on electrical live parts. Protection class of the device when
open is IP 00! It is possible to touch hazardous voltages directly.
11
Enclosure
11.1
Technical data
Type
Part-No.
Rated cur-
rent
{1}
Rated tem-
perature
Max. line
fuse
{2}
Integrated semi-
conductor fuse
{3}
Max. Heat
dissipation
approx.
{4}
Weight
[A]
[
°
C]
[A]
[Part.-No.]
[W]
[kg]
PXET6Q
303612
6
45
10
M 10 A 5x20 mm
20
1.3
PXET10Q
303613
10
40
16
FF20 A 6x32 mm
40
2.3
{1}
Rated current se current speci
fi
cation rating plate @ rated voltage, @ rated temperature
{2}
Max. supply side line fuse according to DIN EN 60204-1 classi
fi
cation VDE0113 chapter 1
{3}
Integrated semiconductor fuse in device (no line safety switch)
{4}
At rated voltage, values for different speci
fi
cations on request
Line voltage
(Rated voltage)
1 ~ 230 V (-15...+10 %), 50/60 Hz
(230 V)
Input resistance for sensor or signal
set for the rotational speed
for 0 - 10 V input: R
i
> 100 k
Ω
for 4 - 20 mA input: R
i
= 100
Ω
Output voltage
approx. 0 - 100 % of applied mains voltage
Min. motor current
approx. 0.2 A
Voltage supply e.g. for sensors
+24 V
±
20 %, I
max
250 mA
Output (0 - 10 V)
I
max
10 mA (short-circuit-proof)
Max. permissible ambient temperature 55
°
C
Min. permissible ambient temperature 0
°
C (if mains voltage is not switched off up to -20
°
C)
Permissible installation height
0...4000 m amsl
≤
1000 m: no limitation
> 1000 m: max. permissible output current = current indication name plate minus 5 % /
1000 m
> 2000 m: max. permissible line voltage = max. voltage indication name plate minus
1.29 % / 100 m
Permissible rel. humidity
85 % no condensation
Electromagnetic compatibility for the
standard voltage 230 / 400 V accord-
ing to DIN IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)
Interference immunity EN 61000-6-2 (industrial applications)
Harmonics current
According EN 61000-3-2 (for a
“
professional device
”
)
see Electrical installation / harmonics current
Housing protection
IP54
Operating Instructions
Acontrol
–
model series PXET6Q / PXET10Q
Enclosure
L-BAL-E016-GB 1925 Index 007
Part.-No.
27/32