9.2.2
Example Temperature control
“
Cooling function
”
(factory setting)
•
“
Val > Set = n+
”
(DIP4 =
|
OFF
|
)
•
Temperature sensor type TF..
•
Measuring range controller -26...+76
°
C
Settings
•
set
= 50 % 25
°
C (102 K / 100 % x 50 % - 26
°
C)
•
Pband
= 10 % 10.2 K (102 K / 10 )
U
Motor
50 %
100 %
[°C]
n-min. 0 %, n-max. = 100 %
50 % ^ 25 °C
Set
Pband
10 % ^ 10.2 K
11.03.2008
v_temp_cool_umotor.vsd
35.2 °C
n-min. 35 %, n-max. = 85 %
Idealized principle diagram
9.2.3
Example Temperature control
“
Heating function
”
•
“
Val < Set = n+
”
(DIP4 =
|
ON
|
)
•
Temperature sensor type TF..
•
Measuring range controller -26...+76
°
C
Settings
•
set
= 50 % 25
°
C (102 K / 100 % x 50 % - 26
°
C)
•
Pband
= 10 % 10.2 K (102 K / 10 )
U
Motor
50 %
100 %
[°C]
n-max. = 100 %, n-min. 0 %
50 % ^ 25 °C
Set
Pband
10 % ^ 10.2 K
11.03.2008
v_temp_heat_umotor.vsd
14.8 °C
n-max. = 85 %, n-min. 35 %
Idealized principle diagram
Operating Instructions
Acontrol
–
model series PXET6Q / PXET10Q
Setting for operation
L-BAL-E016-GB 1925 Index 007
Part.-No.
21/32