5.9 Enable, Device ON / OFF (Digital In 1 = D1)
Electronic disconnection and Reset after motor fault via
fl
oating contact at termi-
nals
“
D1
”
-
“
D1
”
•
Device
“
ON
”
for closed contact.
•
Device
“
OFF
”
with opened contact.
•
Relais
“
K1
”
remains energized, terminals 11 - 14 bridged. The signal lamp
fl
ashes in
code
|
1
|
(
Diagnostics / faults)
Activation via
fl
oating contacts, a low voltage of approx. 24 V DC is connected.
Attention!
Never apply line voltage to the digital input!
5.10 Relay outputs (K1)
An external fault indicator is available over the potential-free contacts of the built-in relay
(max. contact rating
Technical data and connection diagram).
For operation the relay is energized, terminals
“
12
”
and
“
14
”
are bridged. For fault the
relay is de-energized, terminals
“
11
”
and
“
12
”
are bridged (
Diagnostics / faults).
•
Fault indicated for: line fault, blown internal semiconductor fuse, broken controller-
internal voltage supply, overheating by the motor (thermostats
“
TB
”
connected).
•
When switching off via enable (D1 = Digital In 1), the relay remains energized.
5.11 Potential at control voltage connections
The connections for the control voltage (< 30 V) relate to the common GND potential
(exception: relay contacts are potential-free). There is a potential isolation between the
connections for the control voltage and the PE conductor. It must be ensured that the
maximum external voltage at the connections for the control voltage cannot exceed 30 V
(between the
“
GND
”
and
“
PE
”
conductor terminals). A connection to the PE conductor
potential can be made if required;
fi
t a bridge between the
“
GND
”
terminal and the
“
PE
”
connection (terminal for shield).