4.3 Outdoor installation

Outdoor installation is possible up to -20 

°

C when the controller supply is not switched 

off. Installation must be protected from the effects of weather as much as possible, 
including protection from direct sunlight! 

4.4 Installation location for agriculture 

When using for animal keeping, do not install the device directly in the stable but in a 
separate room with a lower pollutant load. This helps to avoid damages caused by 
pollutant gases (e.g. ammonia fumes, hydrogen sulphide fumes).

4.5 Temperature in

uences during commissioning

Avoid condensation in the controller and functional faults attributable to condensation by 
storing the controller at room temperature!

5 Electrical installation

5.1 Safety precautions

Danger due to electric current

Work on electric components may only be carried out by trained electricians or by 
persons instructed in electricity under the supervision of an electrician in accordance 
with electrical engineering regulations.

The 5 electrical safety rules must be observed!

It is forbidden to carry out work on electrically live parts.

Cover neighbouring electrical equipment during installation work.

Other measures may be necessary to achieve safe electrical isolation.

A second person must always be present when working on energized parts or lines 
who disconnects  in case of emergency.

Electrical equipment must be checked regularly: Loose connections are to be re-
tightened and damaged lines or cables must be replaced immediately.

Always keep switch cabinets and all electrical supply facilities locked. Access is only 
allowed for authorized persons using a key or special tool.

Operating the device with the housing cover removed is prohibited because 
energized, exposed parts are present inside the device. Disregarding this regulation 
can lead to severe personal injury.

The required protective earth connection is established using screws between the 

Operating Instructions 

Acontrol

 PSET6 / PSET10

Electrical installation

L-BAL-E141-GB 1925 Index 004

Part.-No. 

10/24

Summary of Contents for Acontrol PSET10

Page 1: ...Acontrol PSET6 PSET10 Speed controller for variable voltage 1 fans Operating Instructions Keep for reference L BAL E141 GB 1925 Index 004 Part No english ...

Page 2: ...7 2 9 Employment of external personnel 8 3 Product overview 8 3 1 Operational area 8 3 2 Maintenance 8 3 3 Transport 8 3 4 Storage 8 3 5 Disposal recycling 8 4 Mounting 9 4 1 General notes 9 4 2 Minimum space requirement 9 4 3 Outdoor installation 10 4 4 Installation location for agriculture 10 4 5 Temperature influences during commissioning 10 5 Electrical installation 10 5 1 Safety precautions 10...

Page 3: ...tions 16 6 3 Diagram setting signal and speed 16 6 4 Minimum speed cut off DIP 5 17 6 5 Hardstart function DIP 6 17 6 6 Operation with two variable output voltages two steps 17 7 Start up 18 7 1 Prerequisites for commissioning 18 8 Diagnostics Faults 18 8 1 If controller doesn t work correctly 19 9 Enclosure 20 9 1 Technical data 20 9 1 1 Performance reduction during elevated ambient temperatures ...

Page 4: ...ating instructions at any time Keep the operating instructions for continued use They must be passed on to all successive owners users and final customers 1 2 Target group The operating instructions address persons entrusted with planning installation start up maintenance and servicing who have the corresponding qualifications and skills for their job 1 3 Exclusion of liability Concurrence between t...

Page 5: ... arising from non intended use 2 2 Explanations of symbols Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows Attention General hazardous area Death or severe injury or significant property damage can occur if the corresponding precautions are not taken Danger due to electric current Danger by dangerous electric voltage Death or ...

Page 6: ...gulations Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supervision of an experienced person This also applies to personnel undergoing general training Comply with the legal minimum age 2 5 Start up and during operation Attention During commissioning unexpected and hazardous conditions can arise in the entire installation due to defective ...

Page 7: ...be made on the device All planned modifications must be authorized by the manufacturer in writing Use only genuine spare parts genuine wearing parts genuine accessories from ZIEHL ABEGG These parts were specifically designed for the device There is no guarantee that parts from non original sources are designed and manufactured in correspondence with load and safety requirements Parts and optional eq...

Page 8: ... The controller described is used for continuous speed adjustment on variable voltage 1 motors used to drive ventilators or pumps 3 2 Maintenance The device must be checked for soiling and if necessary cleaned in periodic intervals 3 3 Transport The device is packed ex factory to suit the transport method previously agreed Always use the original packaging materials when transporting the device Av...

Page 9: ...stalled in a location where it will not be disturbed but at the same time can be easily accessed Depending on the housing model use supplied stoppers for cable inlets cut off necessary cable inlets respectively to the cable diameter Or alternative use cable inlet for cable glands Any cable ducts openings not used must be sealed Care must be taken to avoid direct radiation from the sun The device i...

Page 10: ...of an electrician in accordance with electrical engineering regulations The 5 electrical safety rules must be observed It is forbidden to carry out work on electrically live parts Cover neighbouring electrical equipment during installation work Other measures may be necessary to achieve safe electrical isolation A second person must always be present when working on energized parts or lines who di...

Page 11: ...connect the shielding to one side only i e only to the control unit with the protective ground keep cable short and with as little inductance as possible 5 2 3 Harmonics current for devices 16 A According to EN 61000 3 2 these devices are to be classified as professional devices Connection to a low voltage supply public networks is allowed insofar as this has been clarified with the respective energ...

Page 12: ...r noise this noise may be dominant in the lower speed range due to the occurrence of resonance For systems where noise is critical we recommend using our Fcontrol series frequency converters with integrated sinusoidal filter 5 5 Motor protection The motor can be protected by connecting thermostats TB When multiple motors are connected it is essential to ensure that thermostats TB are always connect...

Page 13: ...eter factory setting DIP 8 ON 0 10 V modulation 0 100 Proportional the internal control of modulation with consideration n min and n max setting For enable OFF it goes not back to 0 V For motor fault the output signal remains for a slave controller Master Slave combination 5 8 Voltage supply for external devices 24V GND A voltage supply is integrated for external devices e g a sensor max current l...

Page 14: ...dged Diagnostics faults Fault indicated for line fault blown internal semiconductor fuse broken controller internal voltage supply overheating by the motor thermostats TB connected When switching off via enable D1 Digital In 1 the relay remains energized 5 11 Potential at control voltage connections The connections for the control voltage 30 V relate to the common GND potential exception relay con...

Page 15: ...o touch hazardous voltages directly 09 06 2011 v_pset_intern_bed VSD n max 0 100 n min 0 100 R15 ON OFF 10 9 8 7 6 5 4 3 2 1 DIP S1 R16 Potentiometer n min Minimal output voltage basic speed Setting range 0 100 n min takes priority if over n max Potentiometer n max Maximal output voltage speed limiter Setting range 100 n min Dipswitch S1 Basic setting for device function Operating Instructions Aco...

Page 16: ... Analog Out 1 Constant voltage 10 V for exter nal potentiometer 0 10 V modulation 0 100 9 no function 10 no function 6 3 Diagram setting signal and speed Setting via external signal or external potentiometer Output voltage from approx 0 100 of connected line voltage or in range of settings n min up to n max nM 50 100 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 0 10 V 10 0 V Min Min 0 Max 100 Min...

Page 17: ...ing the mains voltage on the output voltage rises during the firmly programmed run up time to the given value DIP 6 ON Hardstart function ON For a safe starting of the connected fans the function Hard start can be activated After switching the mains voltage on the controller generates for approx 10 sec onds max voltage 100 ignoring any control signal Afterwards the output voltage adjusts itself to ...

Page 18: ...late will not be exceeded 5 Make sure that no persons or objects are in the hazardous area 8 Diagnostics Faults Operating states are indicated by both internal status LEDs by a flashing code Code Relay K1 Explanation Reaction of Controller Adjustment OFF de energized terminals 11 12 bridged No line voltage In the event of a mains interruption the unit switches OFF and auto matically ON when the vol...

Page 19: ...ode 09 06 2011 v_flash_code_pset VSD 2 1 ON OFF 8 1 If controller doesn t work correctly Information Setting of dip switches in principle only when device is not under voltage If the device is on mains supply modifications will partly not be identified and realized Attention It is generally forbidden to carry out work on electrical live parts Protection class of the device when open is IP 00 It is p...

Page 20: ...tor current approx 0 2 A Voltage supply e g for sensors 24 V 20 Imax 250 mA Output 0 10 V Imax 10 mA short circuit proof Max permissible ambient tem perature 55 C Min permissible ambient tem perature 0 C if mains voltage is not switched off up to 20 C Permissible installation height 0 4000 m amsl 1000 m no limitation 1000 m max permissible output current current indication name plate minus 5 1000 ...

Page 21: ...rature above the rated temperature see following table The average value measured during a 24 h period must be 5 K under the max ambient temperature For installation in a switch cabinet the device s dissipation and its possible affect on the ambient temperature must be taken into consideration Maximal motor current depending on ambient temperature Type Part No 40 C 45 C 50 C 55 C A A A A PSET6 303...

Page 22: ...altern with internal thermostats 2 A1 GND Ausgang Output 0 10 V Imax 10 mA 3 E1 GND GND Eingang Input 0 10 V 4 PEUN17K4 08 06 2011 TB TB D1 D1 24V Kontaktbelastung Contact rating max AC 250 V 5 A 5 1 Line 1 230 V 50 60 Hz 2 1 Motor with internal thermostats 3 Output 0 10 V Imax 10 mA 4 input 0 10 V 5 Contact rating max AC 250 V 5 A Operating Instructions Acontrol PSET6 PSET10 Enclosure L BAL E141 ...

Page 23: ...9 3 Dimensions mm PSET6 PSET10 Operating Instructions Acontrol PSET6 PSET10 Enclosure L BAL E141 GB 1925 Index 004 Part No 23 24 ...

Page 24: ...04 info ziehl abegg de http www ziehl abegg de 9 5 Service information If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries outside of Ger many see www zi...

Reviews: