9.2 Pressure control, Air velocity control (PI-Controller)
4.01
9.2.1 Setting for operation as Pressure and air velocity controller
28.08.2008
v_set_pke.VSD
%
0
100
R47
set
set
Setting range: 0 - 100 %
measuring range of sensor
%
0
100
n-min
R
4
8
28.08.2008
v_nmin_pke.VSD
n-min
Minimum output voltage (basic speed)
Setting range: 0 - 100 % (
“
n-min
”
takes priority if over
“
n-max
”
)
28.08.2008
v_nmax_pband_pke.VSD
n-max /
P-band
R
4
9
%
5
30
n-max / Pband
Maximal output voltage (speed limiter)
Setting range: 100 % -
“
n-min
”
9.2.2 Example: Pressure control for ventilation systems
Pressure sensor
•
Type DSG200
•
Measuring range 0 - 200 Pa
•
Output signal 0...10 V
Settings
•
set
= 50 %
100 Pa
9.2.3 Example: Air velocity control for clean rooms
Air velocity sensor
•
Type MAL1
•
Measuring range 0 - 1 m/s
•
Output signal 0...10 V
Settings
•
set
= 50 %
0.5 m/s