Low current noise cutoff Confirmation.

Pressing “

Up” key set displayed value and

will advance to Assignment of Pulsed output to Import or
Export Energy menu. (See section 3.2.10)

pressing the “

Down” key will re-enter the “Low current

Noise cutoff Edit” mode.

SysV

SysA

Hz

x1000

kWh

x1000

x1000

3.2.10. Assignment of pulsed output to Import or Export Energy

This screen allows the user to assign pulse output1 and pulse output2 to Import or Export energy and vice versa.

Pressing “

Up” key accepts the present Pulsed output

and advance to measurement screens.
(see section 2).

Pressing the “

Down” key will enter the “Assignment of

pulsed output” mode and will toggle Rl1 and Rl2. Assigning
RL1 for Import energy will automatically assign RL 2 for
Export energy and vice-versa.

Assignment of Pulsed output

SysV

SysA

Hz

x1000

kWh

x1000

x1000

Assignment of pulsed output confirmation.

Pressing “

Up” key set the pulsed output2 to

Import energy and pulsed output1 to Export Energy and will
advance to measurement screens. (See section 2)

pressing the “

Down” key will re-enter the “Assignment

of Pulsed output” mode.

SysV

SysA

Hz

x1000

kWh

x1000

x1000

Caution

1.

In th e int eres t o f safe t y an d fu n cti o nali ty th is pr odu ct mu st b e ins tal le d by
a qua li fie d eng in eer, ab id in g by an y l oca l reg u lat io ns.

2.

Vo lta ge s dan ge r ou s to hum an l if e are pr ese n t at so m e o f th e te r m in al
co nn ec t io ns o f th is un it . E ns u re tha t al l su p pl ies are d e-en erg ise d b ef ore
att emp ti n g an y co nn ec t io n o r di sc onn ec t io n.

3.

T hes e pr odu ct s d o n ot hav e int ern al fus es th ere f or e ex ter n al f us es mu st
b e us ed to ens ur e sa f et y u nd er f au l t co n dit io ns.

5.1 EMC Installation Requirements

This product has been designed to meet the certification of the EU directives
when installed to a good code of practice for EMC in industrial environments,
e.g.

1.

Screened output and low signal input leads or have provision for fitting
RF suppression components, such as ferrite absorbers, line filters etc., in
the event that RF fields cause problems.

Note: It is good practice to install sensitive electronic instruments that are
performing critical functions, in EMC enclosures that protect against electrical
interference which could cause a disturbance in function.

2.

Avoid routing leads alongside cables and products that are, or could be,a
source of interference.

3.

To protect the product against permanent damage, surge transients must
be limited to 2kV pk. It is good EMC practice to suppress differential
surges to 2kV at the source. The unit has been designed to automatically
recover in the event of a high level of transients. In extreme
circumstances it may be necessary to temporarily disconnect the
auxiliary supply for a period of greater than 5 seconds to restore correct
operation.

4.

ESD precautions must be taken at all times when handling this product.

The Current inputs of these products are designed for connection in to
systems via Current Transformers only, where one side is grounded.

5.2 Case Dimension and Panel Cut Out

3.78”

96mm

FRONT DISPLAY

AREA

3.78”

96mm

3.15”

80mm

3.62”

92mm

PANEL CUTOUT

3.62”

92mm

MAX PANEL THICKNESS 0.18”,5mm

5. Installation

Mounting is by four side clamps, slide the side clamps throu gh side slot till side clamp
gets fir mly locke d in a groove (Refer fig.) Consideratio n should be given to the space
required behi nd the inst ru ment to allo w for bends in the connect ion cables.

As the front of the enclosure conforms to IP54 it is protected from water spray
from all directions, additional protection to the panel may be obtained by the
use of an optional panel gasket. The terminals at the rear of the product
should be protected from liquids.

The

should be mounted in a reasonably stable ambient

Ziegler

mfm

3420

temperature and where the operating temperature is within the range

0

-10 to 55 C . Vibration should be kept to a minimum and the product should
not be mounted where it will be subjected to excessive direct sunlight.

SLIDE IN THIS DIRECTION AND LOCK

PANEL

Ziegler mfm 3420

4. Pulse output option

The pulse output gives pulses at the rate proportional to the measured active energy kWh.
There are two options available,
1) One Pulse Output: Relay 1 can be configured either to Import Active energy or

Export Active energy.

2

The pulse divisor and pulse width (duration) can be configured. When two pulse outputs
are fitted

,

they share a common divisor value and pulse width

) Two Pulse Output: Here it is possible to assign Import Active energy either to Relay1

or Relay 2. Then accordingly Export Active energy is configured
automatically to the corresponding relay.

.

NOTE:

If system power is selected in W then default pulse rate is 1 pulse per Wh (upto 3600W).
If the system power is scaled in kW then default pulse rate is 1 pulse per kWh
(upto 3600 kW). If the system power is over 3600 kWh then pulse rate is 1 pulse per MWh.

www.ziegler-instruments.com

5

|

7

Summary of Contents for mfm 3420

Page 1: ...Sys Voltage Current SysV SysA Hz x1000 kWh x1000 x1000 SysV SysA Hz x1000 kWh x1000 x1000 SysV SysA Hz x1000 kWh x1000 x1000 1 Introduction The is a panel mounted 96 x 96mm DIN Quadratic Digital Ziegl...

Page 2: ...sing the Up key advances the operation to the Up digit and sets the third digit in this case to 5 New Change Password first digit entered prompting for second digit Decimal point indicates that this w...

Page 3: ...imary Value Confirmation stage The minimum value allowed is 1 the value will be forced to 1 if the display contains zero when the Up key is pressed Current Transformer Primary Value Confirmation This...

Page 4: ...and will advance to Auto scroll menu see section 3 2 7 pressing the Down key will re enter the Pulse Duration Edit mode 3 2 7 Auto Scrolling This screen allows user to enable screen scrolling Pressin...

Page 5: ...3 To protect the product against permanent damage surge transients must be limited to 2kV pk It is good EMC practice to suppress differential surges to 2kV at the source The unit has been designed to...

Page 6: ...es at 10s intervals 0 2VA approx Nominal inputcurrent 1A 5A AC rms programmable at site Max continuous inputcurrent 120 of Rated Value Nominal input current burden 0 6VAappro x Max short duration curr...

Page 7: ...torage temperature Relative humidity Warm up time Shock Vibration Enclosure front only Enclosure 96mmx 96mm DIN Quadratic Polycarbonate Housing Screw type terminals 80 mm 0 620 kg Approx Style Materia...