Fixing instructions  Doc. version 1.0

FBI800

PROFILE Fire detection system

Connects the Fire Brigade Key Depot (FBKD) 
according to DIN 14675 standard.

Connects the Transmit Unit (TU) which trans-
mits the fire alarm to the fire brigade control 
centre. 

Features

The FBI800 slot card is used as the interface 
between the panel and standard fire brigade 
interfaces. It operates with its own system 
address and communicates with MCPU on 
PFI800 over the internal N-Bus.
One FBI800 card can be used in the panel. This 
supports a single serial FBF / FAT. In a system 
with several panels, each panel can have an 
FBI800 with its own FBKD, TU and FBF/FAT 
equipment.

Cabling requirements

Use shielded cables to connect the FBF / FAT, 
FBKD and TU peripherals to FBI800 card. Select 
all cables in accordance with local standards.
Connect the cable shields to the panel earth 
stud. At the peripherals, connect the shields to 
the earth stud or follow the manufacturer's 
instructions. 

Maximum cable resistance

Installation

To install the FBI800 module, complete the fol-
lowing steps:
1 Set the optional jumper J2 to the desired set-

ting. See Table 2. 

2 Set the optional SW3 DIP switches 5, 6 to 

their default positions. Refer to Table 3.

CAUTION

Do not connect the FBKD and TU directly 
to the serial FBF or serial FAT peripherals. 
They are not accessible in the case of 
system fault of the microprocessor on 
FBI800 slot card.

FBI800

Maximum cable 
resistance (per 
conductor)

Serial FBF/FAT 
RS485 lines 
A1, B1, A2, B2

XT1 pins 1 
to 4

20R

Serial FBF/FAT 
power lines 
Ub1, GND1, 
Ub2, GND2

XT1 pins 5 
to 8

15R

FBF-260 pins 1 
& 2, 0V & +Ub

XT3 pins 7 
& 8, PWR- 
& PWR+

20R

FBF-260 pins 3 
to 15

XT3 pins 1 
to 6, XT4 
pins 1 to 4

100R

FSD Heater

XT2 pins 1 
& 2, HEAT+ 
& HEAT-

6R

FSD door 
opener

XT2 pins 3 
& 4, DO 
PWR+ & 
DO PWR-

10R

FSD sabotage 
loop, door con-
tact, sabotage 
LED

XT2 pins 5 
to 10

100R

TU RMS

XT4 pin 5 
FIC

100R

TU +a, TU-b (total resistance 
from FBI800 to FBF-260 to 
TU)

50R

Table 1: Maximum cable resistance

NOTICE

Switch the panel OFF during the 
installation procedure

Summary of Contents for PROFILE FBI800

Page 1: ...EDB2 B PWR1 PWR1 PWR2 PWR2 HEAT HEAT DO PWR DO PWR DO CNT DO CNT SB LP SB LP SB LED SB LED CNOFLED TUOFLED FIALLED ASOFLED TUACLED EXACLED PWR PWR RL1 C RL1 0 C FIALRST AS OFF REV ON TU OFF FIC TU a TU b TU PWR Status Card Fault Reset A d d r e s s 1 0 1 2 3 4 5 6 7 Fig 1 FBI800 Fire Brigade Interface card 1 Serial FBF FAT connector 2 Fire Brigade Key Depot connector 3 Parallel FBF RL1 connector 4...

Page 2: ...e earth stud or follow the manufacturer s instructions Maximum cable resistance Installation To install the FBI800 module complete the fol lowing steps 1 Set the optional jumper J2 to the desired set ting See Table 2 2 Set the optional SW3 DIP switches 5 6 to their default positions Refer to Table 3 CAUTION Do not connect the FBKD and TU directly to the serial FBF or serial FAT peripherals They ar...

Page 3: ... to binary conversion Jumper 1 2 2 3 OPEN J2 RL1 Normally closed con tact Normally open con tact Table 2 Jumper setting for installation SW3 Function ON OFF 1 2 3 4 DIP1 DIP2 DIP3 DIP4 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 5 Boot Mode Active Disabled 6 Debug Mode Enabled Disabled 7 EA Door EA signal activates the FBKD door opener output EA signal doesn t acti vate...

Page 4: ...ult Table 5 Optical indicators on the front panel RX1 Received data Bus1 left Green ON flickering Data is received on the Bus1 left channel OFF permanent Nothing is received on the Bus1 left channel TX1 Transmitted data Bus left Green ON flickering Data is transmitted on the Bus1 left channel OFF permanent Nothing is transmitted on the Bus1 left channel RX2 Received data Bus right Green ON flicker...

Page 5: ...instructions Doc version 1 0 5 8 Wiring Serial FBF FAT FBI800 ERDE Ub1 XT1_5 PWR1 GND XT1_6 PWR1 Ub2 XT1_7 PWR2 GND XT1_8 PWR2 A2 XTI_3 REDB2 A B2 XTI_4 REDB2 B A1 XTI_1 REDB1 A B1 XT1_2 REDB1 B Table 7 Wiring of Schraner serial FBF FAT to FBI800 Transmit Unit FBI800 0V XT4_7 TU b 24V XT4 8 TUPWR RMS XT4_5 FIC b XT4_7 TU b a XT4_6 TU a Table 8 Wiring of Transmit Unit to FBI800 ...

Page 6: ...4_4 TU OFF 7 8 XT4_2 AS OFF 9 10 XT3_5 TUACLED 11 XT3_1 CNOFLED 12 XT3_3 FIALLED 13 14 XT4_1 FIALRST 15 XT4_3 REV ON 16 BMZ A XT4_6 TU a BMZ B XT4_7 TU b UE A to Transmit Unit a UE B to Transmit Unit b Transmit Unit RMS XT4_5 FIC Table 9 Wiring of FBF 260 to FBI800 CAUTION Figure 4 is the parallel FBF installation example only The national standards and local regulations should be considered in th...

Page 7: ...0 and FBF 260 FSD S3 FBI800 K1 XT2_7 SB LP K2 XT2_8 SB LP K3 K4 K5 XT2_3 DO PWR K6 XT2_4 DO PWR K7 XT2_5 DO CNT K8 XT2_6 DO CNT K9 XT2_1 HEAT K10 XT2_2 HEAT K11 XT2_9 SB LED K12 XT2_10 SB LED Table 10 Wiring of FSD S3 to FBI800 S24226 FBI800 FBF 260 X1 1 UE B b 0V X1 2 XT4_8 TU PWR X1 3 X1 4 XT4_5 FIC X1 5 UE B b 0V X1 6 UE A a Table 11 Wiring of Transmit Unit S24226 A12 by Siemens to FBI800 and F...

Page 8: ...detection system Tyco Fire Security GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerland www zettlerfire com 120 515 292_PROFILE AP FBI800 F doc version 1 0 20 July 2017 Subject to change without notice ...

Reviews: